Warnings
181
Warnings
Conflicting parameter inputs (for example minimum operating
frequency PNU A062 > end frequency PNU A004). In addition, the
PRG LED flashes until the parameters are corrected.
The following warnings may be issued:
Display
Function
H001
H201
Maximum operating frequency, PNU A061 (A261)
>
End frequency, PNU A004 (A204, A304)
H002
H202
Minimum operating frequency, PNU A062 (A262)
>
H004
H204
H304
Nominal motor frequency, PNU A003 (A203, A303)
>
H005
H205
H305
Setpoint frequency, PNU F001 or PNU A020 (A220, A320)
>
H006
H206
H306
Fixed frequencies 1 to 15, PNU A021 to A035
>
H012
H212
Minimum operating frequency, PNU A062 (A262)
>
Maximum operating frequency, PNU A061 (A261)
H015
H215
Setpoint frequency, PNU F001 or PNU A020 (A220, A320)
>
H016
H216
Fixed frequencies 1 to 15, PNU A021 to A035
>
H021
H221
Maximum operating frequency, PNU A061 (A261)
<
Minimum operating frequency, PNU A062 (A262)
H025
H225
Setpoint frequency, PNU F001, PNU A020 (A220, A320)
<
H031
H231
Maximum operating frequency, PNU A061 (A261)
<
Increased starting frequency, PNU b082
H032
H232
Minimum operating frequency, PNU A062 (A262)
<
H035
H235
H335
Setpoint frequency, PNU F001 or PNU A020 (A220, A320)
<
H036
Fixed frequencies 1 to 15, PNU A021 to A035
<
H037
Jogging frequency, PNU A038
<
H085
H285
H385
Setpoint frequency, PNU F001 or PNU A020 (A220, A320)
=
Frequency jump 1 to 3
g
jump width, PNU A063 to
A068
1)
H086
Fixed frequencies 1 to 15, PNU A021 to A035
=