01/02 AWB8230-1415GB
Setting the frequency and start
signal parameters
125
Base frequency
The base frequency is the frequency at which the output voltage
has its maximum value.
Maximum end frequency
If there is a constant-voltage frequency range beyond the base
frequency defined with PNU A003, this range is defined with
PNU A004. The maximum end frequency must not be smaller than
the base frequency.
PNU
Name
Adjustable in
RUN mode
Value
WE
Nor-
mal
Exten-
ded
A003
A203
A303
Base
frequency
–
–
30 to 400 Hz
50
Figure 122: Maximum end frequency
f
1
: Base frequency
f
2
: Maximum end frequency
PNU
Name
Adjustable in
RUN mode
Value
WE
Nor-
mal
Exten-
ded
A004
A204
A304
Maximum
end
frequency
–
–
30 to 400 Hz
50
0
f
1
f
2
100
[%]
U
f
[Hz]