Programming the control
signal terminals
01/02 AWB8230-1415GB
116
Digital fault message output
With this function, you can define whether the DV6 issues a 3-bit
encoded signal to digital outputs 11 to 13 or a 4-bit encoded
signal to outputs 11 to 14 when a fault message is issued.
X
Under PNU C062, specify the digital fault message output.
The table below shows all digital fault messages.
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
C062
Digital fault
message
–
j
00
No output to the digital outputs
00
01
3-bit encoded output to digital outputs 11 to 13
02
4-bit encoded output to digital outputs 11 to 14
Digital output
4-bit encoded
3-bit encoded
14
13
12
11
Fault message
Cause
Fault message
Cause
0
0
0
0
None
–
None
–
0
0
0
1
E01 to E04
Overcurrent
E01 to E04
Overcurrent
0
0
1
0
E05
Overload
E05
Overload
0
0
1
1
E07, E15
Overvoltage
E07, E15
Overvoltage
0
1
0
0
E09
Undervoltage
E09
Undervoltage
0
1
0
1
E16
Intermittent mains failure
E16
Intermittent mains failure
0
1
1
0
E30
IGBT fault
E30
IGBT fault
0
1
1
1
E06
Braking device overload
–
–
1
0
0
0
E08, E11, E23
• EEPROM fault
• CPU fault
• GA fault
–
–
1
0
0
1
E10
Fault in current transformer
–
–
1
0
1
0
E12, E13, E35, E36
• External fault message
• Unattended start protection
triggered
• Thermistor fault
• External brake fault
–
–
1
0
1
1
E14
Earth fault
–
–
1
1
0
0
–
–
–
–
1
1
0
1
E21
Overtemperature in power section
–
–
1
1
1
0
E24
Mains phase failure
–
–
1
1
1
1
E50 to E79
• RS 485 fault
• Slot 1 or 2 fault
• Fault 0 to 9
–
–