Programming the control
signal terminals
01/02 AWB8230-1415GB
114
Running time (RNT) and Mains On time (ONT)
The DV6 frequency inverter counts the time for which it is in RUN
mode (the running time) and time for which it is connected to
mains power
V
LN
(the Mains On time). The digital output confi-
gured as RNT becomes active when the running time set under
PNU b034 is exceeded. The digital output configured as ONT also
accesses parameter PNU b043. The ONT output becomes active
when the DV6 is connected to the supply voltage
V
LN
longer than
the time set under PNU b043. You can configure either one of the
digital outputs as RNT or ONT, but not both at the same time.
X
Program one of the digital outputs 11 to 15 as RNT by entering
the value 11 in the corresponding PNU (C021 to C025) or under
PNU C026 for signalling relay contacts K11-K12.
X
Program one of the digital outputs 11 to 15 as ONT by entering
the value 12 in the corresponding PNU (C021 to C025) or under
PNU C026 for signalling relay contacts K11-K12.
Figure 116: Digital output 11 configured as RNT (running time)
Figure 117: Function chart for RNT (running time)
RNT
24 V
50 mA
11
CM2 12
–
+
RNT
FWD/REV
PNU b034
Figure 118: Digital output 11 configured as ONT (Mains On time)
Figure 119: Function chart for ONT (Mains On time)
V
LN
: Supply voltage
ONT
24 V
50 mA
11
CM2
12
13
14
15
–
+
U
LN
ONT
PNU b034
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
b034
Running time
or Mains On
time exceeded
–
j
0 to 65530 h
When the time entered her is exceeded, either the digital
output configured as RNT (running time) or the digital
output configured as ONT (Mains On time) becomes active.
0