Programming the control
signal terminals
01/02 AWB8230-1415GB
106
PID control deviation (OD)
The digital output configured as OD is activated when a user defi-
nable PID deviation (of the actual value from the setpoint value) is
exceeded. The OD output remains active as long as this differential
is exceeded.
X
If you configure a programmable digital output as OD, you must
also, under PNU C044 enter the threshold at which the OD
signal will activate when the value is exceeded.
X
Program one of the digital outputs 11 to 15 as OD by entering
the value 04 in the corresponding PNU (C021 to C025) or in
PNU C026 for signalling relay contacts K11-K12.
Figure 107: Digital output 11 configured as OD (PID control deviation)
OD
24 V
50 mA
11
CM2
12
13
14
15
–
+
Figure 108: Function chart for OD (PID control deviation)
a
Setpoint
b
Actual value
PNU C044
PNU C044
OD
a
b
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
C044
PID regulator
deviation
–
j
0 to 100%
If the deviation between the setpoint and actual value
exceeds the value entered here when PID control is active,
the OD signal is activated.
3.0