Appendix
01/02 AWB8230-1413GB
164
Cables and fuses
The cross-sections of the cables and line protection fuses used
must correspond with local standards. The values are laid out for
three-phase 400 V mains connection.
Use cables with a larger cross-section for supply voltage and motor
cables which exceed about 20 m in length.
Control signal cables should be screenedandscreened and have a
maximum cross-section of 0.14 to 1.5 mm
2
.
Signalling relay output, cross-section of 0.75 to 1.5 mm
2
. Strip
about 5 to 6 mm off the cable ends.
DF6-340-
L1, L2, L3, U, V, W, PE
VDE
UL
1)
Moeller
mm
2
AWG
11K
M32 A
30 A
PKM0-25
6
8
15K
M40 A
40 A
PKZM4-40
10
6
18K5
M50 A
50 A
PKZM4-50
16
6
22K
M50 A
60 A
PKZM4-50
25
4
30K
M63 A
70 A
PKZM4-63
25
3
37K
M80 A
90 A
NZM7-80N-OBI
35
1
45K
M100 A
125 A
NZM7-100N-OBI
35
1
55K
M125 A
125 A
NZM7-125N-OBI
50
1/0
75K
M160 A
175 A
NZM7-160N-OBI
2
x
35
2
x
1
90K
M200 A
200 A
NZM7-200N-OBI
2
x
35
2
x
1
110K
M250 A
250 A
NZM7-250N-OBI
2
x
50
2
x
1/0
132K
M315 A
300 A
NZM7-250N-OBI
2
x
70
2
x
2/0
1) Approved fuses (class J, 600 V) and fuse holders