Connection to PROFIBUS-DP
70
11/01 AWB2700-1426GB
Process Data
XStart has 1 byte of input data and 1 byte of output data
available. The following table shows the respective struc-
ture:
Table 13: Process data
1) ... only with reversing starters
Process data
Bit
Contents
Value
Meaning
Input data
0
Actual status DIL1
0
OFF
1
ON
1
Actual status DIL2
1)
0
OFF
1
ON
2
Status
PKZM0 0
OFF
1
ON
3
Reserved
0
-
4 to 7
Not assigned
Output data
0
Required status DIL1
0
OFF
1
ON
1
Required status DIL2
1)
0
OFF
1
ON
2
Reserved
0
-
3 Ident-bypass
0
No
tolerance
1
Tolerance not
permitted
4 to 7
Not assigned