background image

Each Mobrey ultrasonic control system requires a 

sensor to suit the specific application, plus a control unit.

These installation  instructions cover the Mobrey control 

units in the MCU200 series. 

1. Sensor installation
2. Control unit installation
3. Applications:

3.1  

Gain adjustment

3.2 

Liquid level alarm

3.3 

Pump control and latching arms

3.4 

Blanket or interface detection

4. Spare parts and fault finding

Contents

Specification

Power supply 

MCU 201 

110/120 ±10%  220/240±10%  50-60 Hz

Installation category 

MCU 201 

II-IEC60664 for 230V ac supply  III-IEC60664 for 115V ac supply

Pollution degree 

MCU 201 

2-IEC60664

Power consumption 

MCU 201 

6VA approx at 240 Vac

Power supply 

MCU 203 

24V dc (20V Min, 30V Max) Supply must be floating or negative earth 

Current consumption 

MCU 203 

0.1A Max

Relay contact rating(s)

 

5A at 230V ac DPCO

Relay state

 

Normal state selectable energised/de-energised   

Relay delay

 

0.5,2,8,30 seconds selectable. Operates for change of relay state in 
one direction only.  50msecs in other direction. (Approx.) 

LED indicators 

Red for alarm,  Green for normal,  Yellow for cable fault

LED state

 

Green/Red indication selectable for either sensor state

Sensors compatible

 

Any Mobrey ultrasonic gap, Hisens or Interface sensor

Sensor frequency

 

Switch selects electronics operational at either l MHz or 3.7 MHz

Cable check

Option selectable for certain sensors

External input

 

Used to hold relay de-energised to provide pump control

Box size

 

200 x 120 x 75mm

Fixing centres 

188 x 88mm

Box rating

 

IP65 Polycarbonate (clear lid)

Temperature

 

-40

o

C to 55

o

C ambient

Holes for glands

 

3 off 16mmØ

EMC

 

EN61326

Safety

 

EN61010-1

Weight

 

equipment weight (mass) 0.700 Kg

WARNING:

If this equipment is used in a manner not specified 

by the manufacturer, the protection provided may 
be impaired.  All installation and commissioning of 
this equipment must be carried out by electrically 
competent persons

Mobrey ultrasonic liquid level control 

or sludge blanket or interface detection 

systems using control unit type MCU200

MCU200

Installation Leaflet

IP227, Rev. 

C

March

 20

19

MCU200 Installation, Operation & 
Maintenance Instructions

www.

delta-

mobrey

.com

Summary of Contents for MCU200 Series

Page 1: ...one direction only 50msecs in other direction Approx LED indicators Red for alarm Green for normal Yellow for cable fault LED state Green Red indication selectable for either sensor state Sensors comp...

Page 2: ...tud before control or signal leads are connected The ground connections must have a current rating of 25A AC SUPPLY Never operate the equipment from a line voltage or frequency in excess of that speci...

Page 3: ...iled to perform an intended operation Equipment has been subjected to prolonged storage under unfavourable conditions Equipment has been subjected to severe physical stress If in any doubt as to the s...

Page 4: ...cal to avoid build up of solids on the sensor faces on either side of the gap In this condition the switching level will be half way up the face if the sensor is mounted from the side of the tank this...

Page 5: ...inal for neutral and one of the 115V or 230V terminals depending on the voltage supply available BEWARE the terminal not connected externally will be live once the transformer is powered via the other...

Page 6: ...l cables attached to the sensors normally these are linked at the sensor to the metal body of the fitting or to each other in the case of non metallic sensors If this continuity is broken the FAULT LE...

Page 7: ...eration of any ultrasonic sensor system This adjusts the gain of the feedback amplifier in the control unit which produces oscillation of the sensor when the coupling between the ultrasonic crystals i...

Page 8: ...e the latching short circuit is applied Only after this circuit is broken can the relay re energise under the control of the sensor A latching alarm can therefore be achieved by connecting one pole of...

Page 9: ...uence of operation to 1 MHz see fig 5 if the sensor will operate at this frequency ii With sensor or pipe in relatively clean water supernatant set gain switch to LO and reduce gain pot see fig 5 unti...

Page 10: ...periodic inspection by a qualified person to ensure that the installation including wiring and equipment housing is safe 5 Spares and fault finding 5 1 The following parts are suitable for replacement...

Page 11: ...r by reflection method Page 11 iv Check the incorrect operation has not been produced by incorrect setting of the frequency selection switch or an external short circuit on the auxiliary input termina...

Page 12: ...ited Riverside Business Park Dogflud Way Farnham GU9 7SS UK 44 0 1252 729140 44 0 1252 729168 mobrey delta mobrey com Linkedin com company delta mobrey ltd Twitter com DeltaMobreyUK Facebook com Delta...

Reviews: