To delete telephone numbers:
SMS command delete 1
st
telephone number:
<CODE> DEL1
.... similar for DEL2...DEL5
In case a foreign number needs to be entered start with 00 follow by the country code (e.g.
0031612345678).
4.4.2 Identification text
It is possible to add a standard identification text (NAME) to all messages sent out by the Mobeye
PowerGuard. The alarm messages are a combination of the name and the alarm text.
A user defined identification has a length of maximum 20 characters. The default identification
text is
‘Mobeye’.
SMS command identification text:
<CODE> NAME:<free text>
4.4.3 Alarm text
Unique alarm texts can be programmed into the Mobeye PowerGuard. User defined texts have a
maximum length of 20 characters.
Following default texts are programmed:
Triggered input 1
<TEXT1>:
Alarm 1
Triggered input 2
<TEXT2>:
Alarm 2
Power failure
<TEXT3>:
Power failure
Power restoration
<TEXT4>:
Power restored
SMS commands text 1:
<CODE> TEXT1:<free text>
SMS commands text 2:
<CODE> TEXT2:<free text>
.... similar for TEXT3 and TEXT4
4.4.4 Alarm notification type: SMS or SMS + call
As default behaviour, after a power failure or an activated input the Mobeye PowerGuard notifies
by SMS text message followed by a telephone call (beep signal). The combination of SMS text
and the call increases the chance of getting the attention of the contact persons. It is possible to
disable the call (OFF), so that only an SMS message will be sent. The default alarm notification
type is ON (SMS + call).
SMS command alarm notification type:
<CODE> CALL:xxx
4.4.5 Power failure delay time
The power failure delay time defines the time that the power fails before an alarm is initiated. If
the power is restored within the delay time, no alarm is sent. The time can be set between 0 and
999 minutes. As default, the delay time is set to 0.
SMS command power failure delay time:
<CODE>
DELAYPOW:xxx
4.4.6 Input type
The input type defines the character of the inputs IN1 and IN2. This can be Normally Open (NO)
or Normally Closed (NC). In case an input is set to NO, the alarm will be triggered as soon as the
terminals of the input are closed. If the input is set to NC, the alarm is triggered in case the
connection between the input terminals is broken. The default input type is set to NO.
SMS command input type input 1:
<CODE> TYPEIN1:xx
SMS command input type input 2:
<CODE> TYPEIN2:xx