6.5.20  Alarm mask 

 

   DTS 4210.timecenter   Moser-Baer AG 

   ==================================== 

 

   ALARMMASK                                    Page 1 

   [ ]=error disabled, [*]=error enabled 

   [*] Bit00: DTS restart             [*] Bit01: System warning 

   [*] Bit02: Supply voltage too low  [*] Bit03: Failure supply 1 

   [*] Bit04: Internal voltage to low [*] Bit05: Error bit5 

   [*] Bit06: Error bit6              [*] Bit07: Error bit7 

   [*] Bit08: Wrong time zone DCF     [*] Bit09: Error Time Zone TC 

   [*] Bit10: Error bit10             [*] Bit11: Error bit11 

   [*] Bit12: Error bit12             [*] Bit13: Oscillator not locked    

   [*] Bit14: GNSS synch lost         [*] Bit15: Time source big offset 

 

   Enter alarm number to alter mask 

 

   Press ENTER for next part, 99 to leave> 

 

Path: 2 Configuration 

 3 Alarms 

 1 Alarm relay 

 1 Alarm mask for relay

 

Display of all the DTS 4210  alarms (64)  on 4 pages. Pages can be scrolled through 
with ENTER. 

An alarm on the current page can be switched on or off by entering an error number. 
The page can be exited with 99. The modifications will be saved or restored one menu 
level higher in “ALARM CONFIGURATION“. All Alarms with “error  bitxx“ are not yet 
used. 

A description of individual errors can be found in appendix "B Time zone table“ 

 

MOBA-NMS:

 Tab: Alarms 

 Alarm mask 

 

 

Summary of Contents for 121059

Page 1: ...ING AND INSTRUCTION MANUAL DTS 4210 timecenter Network Time Server and Master Clock Important Note This Manual is applicable for Firmware version 2018 11 27 and newer For older Firmware version please...

Page 2: ...omposed with the utmost care in order to explain all details in respect of the operation of the product Should you nevertheless have questions or discover errors in this Manual please contact us 3 We...

Page 3: ...Installation 15 6 Operation 16 7 Updates 70 8 Time administration 76 9 SNMP 89 10 Redundant Power supply 93 Appendix A Connection diagrams 94 B Time zone table 104 C Alarm list 106 D Troubleshooting 1...

Page 4: ...Alarms 48 6 5 19 Alarm relay 48 6 5 20 Alarm mask 49 6 5 21 E mail 50 6 5 22 SNMP traps 52 6 5 23 General settings 54 6 5 24 Network 55 6 5 25 Link aggregation LAG 59 6 5 26 IPv4 static routing 60 6...

Page 5: ...a 99 A 3 2 Installation of the lightning protection 99 A 3 3 Distance between antenna and DTS 4210 100 A 3 4 Inline amplifier 101 A 4 Plug in spring terminals 103 B Time zone table 104 C Alarm list 10...

Page 6: ...ecenter is a primary reference clock PRC Grandmaster and Timeserver for the high accurate synchronization of various equipment s and for the use in large network environments It receives time informat...

Page 7: ...installation site To avoid any operating problems keep the device away from moisture and avoid dust heat and direct sunlight Do not use the device outdoors The device is designed for 19 racks and sho...

Page 8: ...nnot rectify this problem yourself 2 2 Cleaning Please make sure that the device remains clean especially in the area of the connections the control elements and the display elements Clean your device...

Page 9: ...various equipment s and for the use in large network environments It can be synchronized over GNSS PTP High Precision DCF and E1 Equipped with a Rubidium Oscillator it has very high holdover accuracy...

Page 10: ...59 3 6 DTS Distributed Time System DTS Distributed Time System is a system developed by Moser Baer AG to distribute time information to decentralized master clocks slave clock lines and time servers o...

Page 11: ...e set as required For DTS devices all communication is conducted over SNMP V3 The SFTP protocol is used for broadcasting files Overview of MOBA NMS functions for DTS devices and network clocks automat...

Page 12: ...OK No power supply Alarm Red On Off The alarm relay signalizes an alarm No active alarms Sync Green On Off DTS 4210 is synchronized to the time source No synchronization to the time source No output...

Page 13: ...r Status Description LAN SFP control lamps Upper Yellow Blinking Off Network activity No activity Lower Green On Off Link 100 Mbit 1 Gbit No Link LAN RJ45 control lamps Left Green On Off Link 100 Mbit...

Page 14: ...dress LAN 2 IPv6 address LAN 3 Power Supply 1 Power Supply 2 Alarm summary Current alarms The display can be operated by means of the corresponding Display button First press the button briefly Switch...

Page 15: ...g appears on the display during the booting procedure the display is dark and empty The display starting remains until the time of output to the lines The duration depending on the configuration is 15...

Page 16: ...Changing the password see chapter 6 5 21 General settings Only one menu can be open at any time The first menu started has priority The menu is automatically closed after 15 min without operation and...

Page 17: ...tion to the selected menu items are displayed in the response line The input line shows the current input values or options possible The status line only appears when an information has to be displaye...

Page 18: ...terminal menu and designated accordingly Example The terminal menu Configuration Alarms can be found in MOBA NMS under the tab Alarms Configuration example of a DTS 4210 timecenter For further details...

Page 19: ...Status menu The status menu consists of 2 pages Status menu page 1 DTS 4210 timecenter Moser Baer AG CLOCK STATE Page 1 2 1 Alarm state 2 Alarm history 3 Time state 4 Time source 5 GNSS 6 Info networ...

Page 20: ...stem information display internal status regulation voltage of the oszillator This information is for support purposes only 8 Product information like serial number firmware version etc 9 All respecti...

Page 21: ...Time source current time source Last time info from source time of the last information from source Offset to source offset to source source system time Jitter of the source current jitter Quality of...

Page 22: ...MOBATIME 22 124 801203 10 MOBA NMS Tab Overview Frame Time time state...

Page 23: ...ured offset 0ns Stability Deviation 12ppb Leap status No leap second detected Date of next leap second Adj direction None None 99 Return Enter desired menu number Path 1 Status 4 Local source enter 2x...

Page 24: ...ice Ping DTS 4210 timecenter Moser Baer AG NETWORK PING 1 Select LAN interface 1 4 1 2 Select IP configuration 1 2 1 3 Destination IP address 192 168 0 20 5 Execute ping command 99 Return Enter desire...

Page 25: ...mecenter Moser Baer AG PTP INFO DEVICE LAN2 IP1 PAGE 1 3 State MASTER Offset to Master 0ns PathDelay E2E 0ns PathDelay P2P 30ns ClockClass 6 ClockAccuracy 0x21 TimeSource 0x20 99 Return Enter desired...

Page 26: ...time source time keeping etc See chapter 6 5 8 Time handling 3 Alarm settings alarm relay e mail SNMP See chapter 6 5 16 Alarm 4 General settings of the DTS 4210 language time zone for alarms and dis...

Page 27: ...Serial lines 4 IRIG outputs 5 E1 signals 6 NTP slave clock time zone server 99 Return Enter desired menu number Path 2 Configuration 1 Outputs 1 DCF Output see chapter 6 5 2 2 Pulse Frequency output s...

Page 28: ...on 6 5 3 Pulse Frequency output 10 MHz output The DTS 4210 is equipped with 8 pulse frequency interfaces The signals are each available on the BNC connectors Pulse and 10 MHz In addition 4 of the puls...

Page 29: ...1 1 Select mode Line switched off on 2 Select time zone see chapter 6 5 30 Time zone selection 3 Com mode 1 send RS 232 receive is not enabled 2 send and receive RS232 3 send and receive RS485 4 send...

Page 30: ...Serial line Serial out 1 8 Telegram file The copy procedure of telegram files is explained in chapter 7 10 Copying Telegram files to the DTS MOBA NMS Frame Serial e g Interface 1 click on Change 1 To...

Page 31: ...the output voltage level 2000 4000 mV The defined voltage corresponds to the expected output amplitude when power matching impedance matching with a load of 50 Ohms is fulfilled The output voltage is...

Page 32: ...s clock line a world time function can be realized DTS 4210 timecenter Moser Baer AG NTP SLAVE CLOCKS AND TIME ZONE SERVER 1 Mode 0 off 1 NTP 2 NTP TZ 3 TZ 4 TZ poll 0 2 Multicast address 3 Multicast...

Page 33: ...it s possiible to set the own IP as gateway Notice Redundant Multicast time server If two NTP servers in the same network should send NTP with the same Multicast IP address redundancy then the first t...

Page 34: ...u page MOBA NMS Tab Outputs Frame NTP slave clocks time zone server 1 Time zone server in Unicast mode Set Mode to Time zone server on req 2 Click on Time zones to define the list of time zones sent t...

Page 35: ...djustment configuration see chapter 6 5 10 Time adjustment Time keeping Redundant operation see chapter 6 5 11 Redundant operation NTP Authentication see chapter 6 5 12 NTP For setting the time manual...

Page 36: ...min 2 160min default 1 Error loss of time source TO 3 DTS stratum 0 Stratum is automatically calculated according to the time source 1 15 Stratum DTS 4210 is set by means of the description in the tab...

Page 37: ...de manual 98 Return and save 99 Return and discard changes Enter desired menu number Path 2 Configuration 2 Time handling 1 General source setting Source configuration 1 6 Source PriorityX 0 NONE 1 GN...

Page 38: ...device supports adjustment only therefore parameter is not configurable 2 Maximum catch up speed Depending on installed Oscillator type Fixed to 1ns s for this device 3 Time core type Standard 0 0 255...

Page 39: ...15 Redundant operation of 2 DTS 4210 6 5 12 NTP Up to 16 multicast or broadcast addresses can be configured DTS 4210 timecenter Moser Baer AG NTP SERVER CONFIGURATION GENERAL PAGE 1 5 1 NTP Authentica...

Page 40: ...Export keys to ram directory The current ntp keys file is written in the directory ram 3 Select the trusted keys separated by space 4 Select the request key 5 Select the control key 6 Set the auto ke...

Page 41: ...roadcast ENTER without entering an address will delete the entry 2 Interval for sending out the NTP information in seconds The interval is rounded after the entry to NTP standard which only permits va...

Page 42: ...Master 200ns 98 Return and save 99 Return and discard changes Enter desired menu number Path 2 Configuration 2 Time handling 5 PTP function 14 PTP slave settings 1 LAN interface for the PTP time sour...

Page 43: ...Moser Baer AG PTP CONFIGURATION config 1 PAGE 2 3 8 Domain 0 9 LOG Announce interval 1 2 second 10 LOG Sync interval 0 1 second 11 LOG Delay Request interval 0 1 second 12 Announce TO 3s 13 Sync TO 3s...

Page 44: ...ty 128 98 Return and save 99 Return and discard changes Enter desired menu number Path 2 Configuration 2 Time handling 5 PTP function 1 PTP config 1 Enter Enter 15 Master Only 0 False 1 True default 0...

Page 45: ...onfiguration 2 Time handling 6 GNSS settings 1 Total Antenna delay ns 0ns 2 Fixed Position Mode FPM 0 off 1 on 0 3 FPM minimum observation time sec 86400sec 4 FPM minimum position accuracy mm 1000mm 5...

Page 46: ...f the hardware delay We recommend that a second source is used to calibrate the DCF Only a high precision DCF signal e g from another DTS 4160 4210 or from GPS 4500 or GNSS 3000 is supported The recei...

Page 47: ...2 Correct time in ns backwards Range 1 000 000 000ns Time is set with ENTER 3 Leap second mode 0 off 1 Additional second will be inserted at entered time Is set to 0 off after inserting the leap seco...

Page 48: ...see chapter 6 5 22 6 5 19 Alarm relay DTS 4210 timecenter Moser Baer AG ALARM CONFIGURATION 2 1 Alarmmask for relay 98 Return and save 99 Return and discard changes Enter desired menu number Path 2 Co...

Page 49: ...14 GNSS synch lost Bit15 Time source big offset Enter alarm number to alter mask Press ENTER for next part 99 to leave Path 2 Configuration 3 Alarms 1 Alarm relay 1 Alarm mask for relay Display of all...

Page 50: ...20 Alarm mask Changes are stored or reset on the overlying menu page MAIL CONFIGURATION 3 IP address of the mail server e g 10 249 34 5 ENTER without entering an address will delete the entry 4 Mail s...

Page 51: ...n 3 Alarms 2 E Mail Enter 11 Authentication mode 0 off sender e mail address used for authentication 1 auto tries CRAM MD5 LOGIN PLAIN in this sequence 2 PLAIN 3 LOGIN 4 CRAM MD5 12 User name only for...

Page 52: ...plies to alarm and alive traps 2 Alarm mask for SNMP trap messages see chapter 6 5 20 Alarm mask Changes are first stored or reset on the overlying menu page SNMP TRAP CONFIGURATION 3 Trap community s...

Page 53: ...rn and save 99 Return and discard changes Enter desired menu number Path 2 Configuration 3 Alarms 3 Traps 4 Configuration of destination 1 1 Address of the evaluation system e g 10 240 0 9 ENTER witho...

Page 54: ...urn and discard changes Enter desired menu number Path 2 Configuration 4 General Device Display language 2 Setting the time zone for the display and also all alarm logs e mail and SNMP See chapter 6 5...

Page 55: ...er Baer AG NETWORK INTERFACES 1 LAN 1 2 LAN 2 3 LAN 3 4 LAN 4 5 LAN 5 6 LAN 6 7 LAN 7 8 LAN 8 9 LAN 9 10 LAN 10 11 LAN 11 12 LAN 12 13 LAN 13 14 LAN 14 15 LAN 15 16 LAN 16 99 Return Enter desired menu...

Page 56: ...ost names may only contain letters capitals or small letters and numerals 0 9 In addition the minus sign may also be used as long as it is not at the end Everything else is not permitted 5 Set domain...

Page 57: ...ration 5 Network 1 LAN 1 Enter 11 Configuration of link aggregation 12 VLAN configuration for IP1 select predefined VLAN config 1 16 0 off See chapter 6 5 27 VLAN configuration 13 VLAN configuration f...

Page 58: ...d via this point Notice DHCP on if no DHCP server is available leads to longer start up time approx 60 sec of the DTS 2 8 Set IP address subnet mask gateway and DNS server Format 10 240 98 7 Network c...

Page 59: ...AG1 LAN6 for LAG2 1 Link aggregation on or off 2 LAG Mode 0 Round robin fault tolerance and load balancing 1 Active backup only one slave in the bond is active fault tolerance 2 Balance XOR fault tole...

Page 60: ...or IP1 and IP2 can be defined DTS 4210 timecenter Moser Baer AG NETWORK IPV4 STATIC ROUTING LAN 1 1 IP1 network destination 1 Prefix 0 0 0 0 24 2 IP1 network destination 2 Prefix 0 0 0 0 24 3 IP2 netw...

Page 61: ...rn and discard changes Enter desired menu number Path 2 Configuration 6 VLAN configuration 1 VLAN config 1 1 Name of the VLAN Max 64 characters 2 Setting the VLAN ID 1 4094 3 Priority Code Point accor...

Page 62: ...n DTS 4210 timecenter Moser Baer AG NETWORK SERVICES 1 telnet on 2 ftp on 3 ssh scp sftp on 98 Return and save 99 Return and discard changes Enter desired menu number Path 2 Configuration 7 Services F...

Page 63: ...out MIB 2 traps the trap community and the destination address must at least be configured in menu 2 Configuration 3 Alarms 3 Traps See also chapter 6 5 22 SNMP traps 2 Alarm mask for SNMP status see...

Page 64: ...oup membership for GET PUT Standard rwmobatime Notice Each configuration change leads to a restart of the DTS SNMP Agent 6 5 31 SNMP V3 DTS 4210 timecenter Moser Baer AG SNMP V3 CONFIGURATION 1 User 1...

Page 65: ...ration 1 User 1 config uration DTSUser1 1 Password for authentication MD5 and privacy DES 8 40 characters 2 Minimal security level 1 noauth no authentication 2 auth only authentication 3 priv authenti...

Page 66: ...2 4 4 Exclude OID 1 2 5 Exclude OID 2 2 6 Exclude OID 3 2 98 Return and save 99 Return and discard changes Enter desired menu number Path 2 Configuration 8 SNMP 6 SNMP V3 security configuration 3 Acce...

Page 67: ...19 9 Tokyo Enter requested time zone Press enter for next part ESC to leave Display of all the DTS 4210 time zones 100 over several pages The pages can be scrolled through with ENTER A time zone can...

Page 68: ...a software update files must first be put on to a USB stick and this stick must be connected to the DTS 4210 See chapter 7 Updates The command always leads to a restart of the DTS 4210 even if no fil...

Page 69: ...can be released by clicking with right mouse button to the device and selecting Commands The Commands menu can be also opened by clicking on Command Icon The following functions can be started via Me...

Page 70: ...4160_dts4210rootfs ubifs dts4160_dts4210cfg ubifs dts4160_dts4210uImage dts4160_dts4210devicetree dtb Additionally the file dts4160_dts4210check md5 must exist all file names are case sensitive Steps...

Page 71: ...cedure the versions should be verified after the update 7 4 Updating images via USB Possible images are dts4160_dts4210u boot dts4160_dts4210app ubifs dts4160_dts4210rootfs ubifs dts4160_dts4210cfg ub...

Page 72: ...message Update in progress appears and at the same time Please wait is shown in the command line All applications are copied The DTS 4210 is automatically restarted on completion of the update The Te...

Page 73: ...also enter ftp dts 10 241 0 5 ram Establish connection with IPv6 The address must be written in brackets e g with Internet Explorer enter ftp dts fd03 4432 4646 3454 2000 Notice The file has to be co...

Page 74: ...nts that are to be saved In case of doubt select everything 4 Click button Next 5 Indicate destination file by clicking the Browse button 6 Optionally enter a free backup comment E g reason for the ba...

Page 75: ...dures telegram files can be copied via FTP or USB stick to the DTS 4210 The copy procedure can be started on DTS 4210 by selecting the menu 3 Maintenance 8 Copy telegram files and press ENTER Afterwar...

Page 76: ...E1 LAN Multicast Devices DCF Outputs UTC Master Clock NTP A B C D Display Operation Error report F PTP GPS SyncE External DCF Timesource Time Zone Entry Time Zone Entry Time Zone Entry Time Zone Entry...

Page 77: ...he available time sources 1 On system startup the DTS waits until the oscillator reaches stable state 2 Then it waits for an available source to set system time usually it uses the first source that i...

Page 78: ...MOBATIME 78 124 801203 10...

Page 79: ...longer it takes to reach high holdover accuracy Holdover accuracy increases over time hence the longer synchronized the higher is the accuracy in holdover Short term time frequency stability When the...

Page 80: ...tep Stratum increase is stopped at configured Stratum limit E g the Stratum timeout is like before 2 hours increasing of the Stratum every 8 minutes the Stratum limit is set to 12 These means after 8...

Page 81: ...ted deviation this means the more stable a source the better its rating DTS will switch immediately to priority 3 source E1 because its deviation is lower than the one of PTP meaning in this scenario...

Page 82: ...be cleared when the leap second mode is changed to no leap second Manual user input To ensure that the leap second adjustment process starts at the exact time the leap second may be configured manuall...

Page 83: ...of dates of the UTC second markers will be as the following Example end of the year 1 Second December 31 23h 59m 59s December 31 23h 59m 59s January 01 00h 00m 00s 1 Second December 31 23h 59m 57s Dec...

Page 84: ...will not be used for synchronization The DTS 4210 must be correspondingly configured to be able to use NTP authentication chapter 6 5 12 NTP The NTP service of the other equipment e g server PC must...

Page 85: ...udel edu mills proto html or on the NTP homepage http www ntp org Autokey is currently defined in an IETF draft https tools ietf org html draft ietf ntp autokey 08 The configuration of Autokey is expl...

Page 86: ...ed of 32 channels and the data rate supported by each channel is 64 kBit s The DTS 4210 is equipped with 4 E1 interfaces Outputs 4 unbalance E1 outputs BNC 75 Ohms TX and RX 4 balanced E1 outputs RJ48...

Page 87: ...lave supervises the system time on the basis of its own GPS time and generates an error message should the time difference amount exceed the configurable value of n nanoseconds Starting the devices wi...

Page 88: ...ains in master mode and the slave changes from slave to master mode But both devices release an alarm NTP The NTP clients select the server with the better lower stratum PTP Clients use BMCA Best Mast...

Page 89: ...ent supports user validation authentication MD5 and encoding encryption DES MIB II values like sysDescr sysContact sysName or sysLocation can only be modified over the DTS menu but not via SNMP The fo...

Page 90: ...n from the MIB files Example Management System DTS Put dts4210FTPMode 1 Variable is set to 1 internally Put dts4210NetServicesConfigCmd 1 Configuration group is assumed Sends dts4210ConfigChanged Noti...

Page 91: ...TimeTicks 4 Bytes dts4210NetworkLAGIFEntry dts4210NetworkIPCfgConfigChangedTime TimeTicks 4 Bytes dts4210NetworkIPCfgEntry dts4210NetworkVLANConfigChangedTime TimeTicks 4 Bytes dts4210NetworkVLANCfgEn...

Page 92: ...4 Bytes Contains the internal system status 66309 dts4210SysAlarms Byte Array 8 Bytes 64 Bit Alarm flags 1 Byte Bit 0 7 2 Byte Bit 8 15 8 Byte Bit 56 63 FFF870FF FFFFFFFF 5 Byte 2 Byte 1 Byte 9 3 6 Al...

Page 93: ...To guarantee a full surveillance of the inputs following variants are possible Power Supply1 Power Supply2 AC In 1 DC In 1 AC In 2 DC In 2 x x x x x x x x Supply is checked once per minute for correc...

Page 94: ...of the connection 3m Connections between female connector 1 SUB D 9 1 and female connector 2 SUB D 9 2 SUB D 9 1 SUB D 9 2 Receive Data 2 3 Transmit Data Transmit Data 3 2 Receive Data Data Terminal...

Page 95: ...V Ground 2 DC in 1 power supply GND 3 DC in 2 power supply Input for external DC supply 24 28V Ground 4 DC in 2 power supply GND 5 Alarm relay Alarm contact open when alarm is active Max load 30 W 30...

Page 96: ...ration Supervision SNMP Telnet SSH Redundant Link to other DTS 4210 Multiple IP addresses 802 3ad LAG 802 1Q tagged VLAN 802 1p prioritized VLAN LAN1 LAN2 LAN3 LAN4 LAN5 LAN6 LAN7 LAN8 LAN9 LAN10 LAN1...

Page 97: ...R A C IRIG B1xx and DCF FSK output analog BNC female 10MHz 10MHz frequency output 50 Ohms BNC female F IN Frequency input future option BNC female Puls Pulse output 50 Ohms Puls Out RS422 RS422 output...

Page 98: ...DCF Out 1 4 DCF output DCF output current loop passive Umax 30VDC Ion 10 15mA Ioff 1mA 20VDC DCF output DCF In DCF input DCF current loop input for the connection of a GPS4500 GND Sup DC output 28 VD...

Page 99: ...ion with open view to the sky The minimum viewing angle for correct functioning is 90 With a viewing angle of less than 90 it is to be expected that the device will not be able to receive a signal at...

Page 100: ...alculated with the minimum amplifier gain The attenuation of the lightning protector is 0 2 dB The maximum cable length for specific cable types manufacturer Huber Suhner are listed in the table below...

Page 101: ...G 58 C U Cable A plus Cable B should not be longer than 37 m Cable C should not exceed 26 m Inline Amplifier Tallysman TW127 Nominal gain 25 dB 4 0 dB typ Impedance 50 Ohms Noise figure 2 dB typ Opera...

Page 102: ...ture range 40 C to 85 C Weight 650g without mounting kit Humidity 95 For complete antenna data sheet please see http www antenna com apg_products cgi id_num 11209 Lightning protection 3402 17 A Huber...

Page 103: ...A 3 3Distance between antenna and DTS 4210 Minimal amplifier gain 19 2 dB Maximum noise figure 1 5 dB Polarization Right hand circular Operating DC voltage 5V Max current 100mA with inserted inline am...

Page 104: ...amabad Karachi Yekaterinburg 5 No 15 Mumbai Kolkata Chennai New Delhi Colombo 5 5 No 16 Astana Thimphu Dhaka Novosibirsk 6 No 17 Bangkok Hanoi Jakarta Krasnoyarsk 7 No 18 Beijing Hong Kong Singapore T...

Page 105: ...o be defined manually in the user time zone table entries 80 99 Legend UTC Universal Time Coordinate equivalent to GMT DST Daylight Saving Time DST Change Daylight Saving Time changeover Standard DST...

Page 106: ...rce big offset Big offset to timesource detected check time source 16 Time source lost Stratum too high check time source 17 Failure time source TO No time information from the selected time source wi...

Page 107: ...ee alarm bit 39 46 serial line5 Tele file invalid See alarm bit 38 See alarm bit 38 47 serial line5 Wrong time zone See alarm bit 39 See alarm bit 39 48 serial line6 Tele file invalid See alarm bit 38...

Page 108: ...ously After initial operation it may take up to 7 days until optimal accuracy is reached with GPS reception Time correction was carried out manually 5 System software update The system software can be...

Page 109: ...e C See chapter E 2 Syntax of the telegram configuration file Telegram time The telegram always contains the time information for the next second for periodical telegram output The telegram content is...

Page 110: ...output sequence The formats and variables available can be seen below TS d d String with Format information TV var1 var2 Variables list Control and special characters String beginning end xFE h FE By...

Page 111: ...ble in ASCII 0 9 A F 1B Definitions CHS Sum of all bytes up to CHS AND h FF XCH XOR link of all bytes up to CHS e g time telegram with following format 36 ASCII characters Date tt mm yy Time hh mm ss...

Page 112: ...2 9 n 2 Quit no telegram output n 3 Telegram output immediately singly n 4 Telegram output at the next second singly n 5 Telegram every second n 6 Telegram every minute n 7 Telegram hourly n 8 Telegr...

Page 113: ...nt no announcement announcement 2 entries AK 0 1 Text table season status 0 no announcement winter 1 announcement winter 2 no announcement summer 3 announcement summer 4 entries ST A B C D Text table...

Page 114: ...PYING OpenSSL SSL Lib 1 0 2g BSD style LICENSE OpenSSH SFTP server 7 9p1 BSD LICENCE dropbear SSH server 2018 76 MIT style Free party BSD LICENSE wide dhcpv6 DHCPv6 client 20080615 Free COPYRIGHT zlib...

Page 115: ...GPS to Pulse Freq CL and RS422 typ 10 s GPS to serial output typ 10 ms jitter 10ms GPS to SyncE G 811 G 812 G 813 compatible GPS to E1 G 811 G 812 G 813 compatible Notice NTP reception DTS 4210 as ser...

Page 116: ...AN 2 VLANs per port can be defined max 32 VLANs LAG 4 LAG are available for LAN ports 2 3 6 7 10 11 14 15 802 3ad only first port has to be configured 12 Network interfaces 100 1000BaseT Data transmis...

Page 117: ...3 different electrical outputs with the same signal passive current loop output opto coupler Imax 10 mA Umax 50 VDC RS422 BNC connector 50 Ohms no load 5 V with 50 Ohms load 2 5 V 10MHz outputs 4x 4 o...

Page 118: ...n socket for mini GBIC module GigaBit Interface Converter 1000Mbps 3 3V with LC connector Recommended module for Multimode fibres D Link DEM 311GT SX 850 nm Maximal cable length depends on type of cab...

Page 119: ...5 DES Data Encryption Standard 84 DHCP 58 DHCPv6 58 Display 14 DST 105 DTS Distributed Time System 10 DTS Link 87 118 E E1 outputs 86 117 E1 settings 46 E1 signals 32 E mail 50 117 F Factory settings...

Page 120: ...SNMP 11 89 116 SNMP alarm notification 92 SNMP alive notification 92 SNMP notification 90 SNMP operation 90 SNMP access configuration 66 SNMP configuration 52 63 SNMP traps 52 90 SNMP user configurati...

Page 121: ...MOBATIME 121 124 801203 10 I Connection table to fill in Line Type Description Example Line Type Description DCF DCF out DCF for master clock ETC1...

Page 122: ...MOBATIME 122 124 801203 10...

Page 123: ...MOBATIME 123 124 801203 10...

Page 124: ...ch www mobatime ch MOSER BAER SA EXPORT DIVISION 19 ch du Champ des Filles CH 1228 Plan les Ouates Tel 41 22 884 96 11 Fax 41 22 884 96 90 export mobatime com www mobatime com MOSER BAER AG Spitalstr...

Reviews: