Microwave with Photocell
Only suitably qualified personnel should install this equipment.
The K4025 is a high-performance, communicating presence detector. The
K4025 is equipped with a regulating photocell to control digital DSI ballasts
(when using the K4025’s Digital Output) and a volt-free output for control of non-
dimmable lighting loads. The K4025 incorporates OneSwitch Dimming, local
manual operation of any controlled lighting load.
Installation and Commissioning
Instructions
Note: K4053 or K4050 required for commissioning
Microwave with Photocell for DSI Ballasts
Flush
Location
The K4025 is an extremely sensitive movement detector; it is essential therefore
that it be installed on a rigid surface that will not itself be subject to movement or
vibration.
Please note that K4025 is not recommended for applications where there are
large surface areas of metal, e.g. metal ceiling or floor tiles, as unpredictable
sensitivity may result.
The units are graded according to four variations in operating frequency. Each
type can be identified by different colour-coding on the detector label and carton.
For reliable operation it is essential that units of the same colour code do not
occupy adjacent positions in open-plan areas (see example below).
Technical Data
MAXIMUM RECOMMENDED MOUNTING HEIGHT: 3.0m
RANGE: Approx 7m dia at 2.4m ceiling height
OFF DELAY: 5-60 minutes - adjustable
PHOTOCELL: Adjustable 50-5000 lux
OPERATING VOLTAGE: 230V 50Hz (UK & Europe)
PRODUCT RATING AND RECOMMENDED CIRCUIT PROTECTION: 10 Amps
MAXIMUM RECOMMENDED LOAD (VOLT-FREE): 6 Amps
MAXIMUM RECOMMENDED LOAD : 25 Ballasts
COLOUR: White
MATERIAL: Flame-retardant ABS
WEIGHT: 300g
IP RATING: 430
Dimensions
72mm
deep
Flange
15mm deep
100mm
50848PL Ed. 1
At the end of their useful
life the packaging and
product should be
disposed of via a suitable
recycling centre.
Do not dispose of with
Yellow
Blue
Red
Green
Red
Green
Yellow
Blue
Red
Green
Yellow
Blue
Yellow
Green
Green
Yellow
Green
Yellow
Yellow
Blue
Red
Green
Red
Green
Yellow
Blue
Red
Green
Yellow
Blue
Blue
Red
Red
Blue
Red
Blue
Yellow
Blue
Red
Green
Red
Green
Yellow
Blue
Red
Green
Yellow
Blue
Yellow
Green
Green
Yellow
Green
Yellow
Yellow
Blue
Red
Green
Red
Green
Yellow
Blue
Red
Green
Yellow
Blue
Blue
Red
Red
Blue
Red
Blue
Electrical Connections
OneSwitch
K4025 should be connected in accordance with the diagrams overleaf.
K4025 is designed to control up to 25 DSI luminaires, a switched load of up to 6
Amps or a combination of the two. The DSI input terminals on the ballasts should
be connected in parallel with each other and to the Polarity-Free Digital Output
terminals on the rear of the K4025. Each DSI luminaire is controlled completely
by its digital input and therefore would normally have a permanent power supply.
Turning the power off to some lights within a control circuit will not have affect the
operation of those lights that remain powered up and under the control of the
K4025.
When switching via the volt-free output multiple K4025s may be connected in
parallel provided the controlled load does not exceed 6 Amps. If digital ballasts
are also being controlled the digital outputs from each detector must not be
mixed even if they are of the same type.
OneSwitch Dimming affords local control to the end-user whereby a simple,
momentary, push-to-make wallswitch can be used to raise or lower the lighting
level or toggle the output of the unit ON or OFF. A short press (less than
1 second) toggles all outputs from
OFF to
ON or from
ON to
OFF. A long press will ramp the digital output either up or down with no effect on
the volt-free output. If the output prior to pressing the switch is above 90% the
output will ramp down; if below 90% it will ramp up. If the latest press and the
current press are within 5 seconds of each other it will ramp in the opposite
direction. A latching switch can be used to override the outputs OFF or ON at
maximum output.
both
both
either
both
Fixing
Please note:
Depth required behind ceiling: 62mm from front flange
Sinking box fits into a 89mm diameter hole in
ceiling tile or plasterboard ceiling.
T
No access above the ceiling is necessary.
Do not position this product on a pitch narrower than 5m.
Do not mount within 0.25m of a luminaire.
plus an allowance for the
minimum bend radius of the cable.
o avoid damage to ceiling tile, do not
overtighten.
SENSORS
K4025 BLU
K4025 YEL
K4025 RED
K4025 GRN
MK Electric
The Arnold Centre, Paycocke Road, Basildon,
Essex, SS14 3EA. UK
Tel: +44 (0)1268 563720
Fax: +44 (0)1268 563064
email: [email protected]
Tel: +44 (0)1268 563000
Fax: 01268 563404
Fax: +44 (0)1268 563365 (International)
email: [email protected]
web site: www.mkelectric.co.uk
Novar ED&S Ltd (A Honeywell Company),
Arlington Business Park, Bracknell, Berkshire, RG12 1EB
All marks in this document identified with a R or TM symbol
adjacent to the mark are Trade Marks of Novar ED&S Ltd.
Technical Help
Customer Service
______________________________________________________