MK Electric Masterseal Plus 56890 Leaflet Download Page 1

B. SERVICE ITEMS

Figure 1

Masterseal Plus™

Switch Modules, Enclosures,

Neon Indicator Modules,

Junction Boxes,

Rated to IP66* 

A. PRODUCT FEATURES

The Masterseal Plus range consists of various surface mounted and flush

mounted products and associated bezels and service items.
The Masterseal Plus range of products are robust and made from a tough

thermoplastic material suitable for interior and exterior use wherever corrosion

resistance, dirt and moisture proofing is required.
All products accept MK push in conduit and cable entries that complement the

range. See Service Items.
All enclosures with external switch rockers have a fluorescent neon locator that

remains lit regardless of the switch position. Replacement neon locators are

available, see Service Items.
If correctly installed, the Masterseal Plus range of products offer an

international protection code of IP66*.
If you are in any doubt regarding this range of products, please contact MK

Technical Sales Service Department on:
+44 (0) 1268 563720 or your local MK representative.
All products conform to their relevant National standard as well as the

standard for enclosures BSEN60439-1, switches to BSEN60669-1and junction

box to BS6220.

*Applies to all products except the Grid Plus enclosure K56414

2

3

C. SAFETY INSTRUCTIONS

WARNING

SWITCH OFF AND ISOLATE THE MAINS SUPPLY BEFORE CARRYING OUT

INSTALLATION OF THE MASTERSEAL PLUS PRODUCT.

1. This product must be installed by a competent person in accordance with

the current editions of the IEE Wiring Regulations (BS7671) and Buildings

Regulations. If in any doubt, consult a qualified electrician.

2. It is essential that all connections are made as instructed that cables are not

stressed and terminals are fully tightened.

3. Where an earth terminal is fitted this should be connected to a protective

earth conductor.

4. If metal conduit is used in more than one cable entry earth continuity must

be maintained between conduits.

5. The neon locator must not be used as a mains status indicator.
6. In junction boxes, four terminal blocks are provided (L, N, E and Loop as

required). Ensure only wires of the same polarity are connected in each

block. Earth and Loop terminals in the mounting box should not be used.

7. At the end of their useful life, the packaging and product should be

disposed of via a suitable recycling centre where facilities exist. DO NOT

BURN.

4

D. INSTALLATION

NOTES:

1. The enclosure is made from polycarbonate which is a highly durable

material, and ideal for most environments. However, if installing in areas

where creosote, some chemicals, synthetic oils and harsh cleaners are used,

seek advice from MK Technical Sales Service Department

2. The enclosure must be mounted on a flat, vertical surface that is free from

grease, dirt and loose material.

3. If the conduit cable entry is from the top or sides the lower drain hole in

the mounting box must be drilled out using a 5mm diameter drill bit. This

will allow any condensation formed in the conduit system to drain out of

the unit. N

ote: opening the drain hole will reduce the IP rating;

therefore ensure that jetted water is not directed at the unit.

4. The drain hole should not be drilled out if the enclosure is to be installed in

an excessively dusty environment. If the drain hole is not drilled out, only

the bottom cable entry must be used.

5. If conduit is used for bottom cable entry, a 5 mm diameter drain hole

needs to be drilled in the lowest point of the conduit run.

6. If wiring directly to the enclosure without conduit and the installation is

outdoors, ensure that a cable specified for outside use is used.

5

INSTRUCTIONS:

CAUTION

Do not allow paint or wood preservative to come into contact with

the product.  The product can be safely mounted on painted surfaces

or surfaces treated with wood preservative when the paint or wood

preservative is completely dry.

1. Read the safety instructions.
2. Mark the position of the fixing holes for the mounting box:

6

Figure 2

3. Drill holes and fit wall plugs suitable for a No. 8 wood screw.
4. Prior to fitting the mounting box to the wall, drill out the drain hole if

required (see Installation Note 3).  File out the complete drain hole profile.

Take care not to damage the internal wall.

5. Carefully remove the cable entry blanks, or drill out rear cable entry, as

required and fit conduit entry (see Service Items).

Figure 3

6. Secure the mounting box to wall with four No. 8 wood screws.  Position

drain hole at bottom left hand corner.

7. Align and install conduit or conduit entry as required.
8. Seal the conduit and cable entry with a non setting conduit sealant such as

Egaweld™ No. 2.  Refer to Figure 4.

8

Figure 4

Mounting Box

Drain Hole

Conduit

Sealant

Conduit
Entry

No 8 Wood Screw

List No.

Description

Dimensions

56890

Neon Locator

31 x 7 dia

56460

Entry Blank

26.9 dia x 5.25

56461

PVC Cable Entry

26.9 dia x 10.15

56462

20 mm Plain Conduit Entry

26.9 dia x 28

56463

20 mm Threaded conduit Entry

26.9 dia x 28

56464

Box Coupler

26.9 dia x 16.5

9933

M20 Earth Lead Adaptor

®

7

Switch and Neon Modules

9. Locate and clip the appropriate switch modules into position on the front

plate as shown in Figure 5.

10. Locate the slots at the TOP of the switch module over the locating lugs at

the TOP of the front plate and press the bottom of the switch module

firmly to snap it into place. TOP is marked on the moulding of the switch

module and the front plate.

11. When a neon module is fitted ensure the module is fitted on the left hand

side (i.e. behind the window in the front plate).

9

10

TO

P

TO

P

TO

P

Press to snap 
into place

Locate Module
on lugs

Figure 5

7. Please note; the colour codes used rigid cabling in the UK prior to April

2004 are as follows:-
RED = terminals marked 'L'
BLACK = terminals marked 'N'
GREEN / YELLOW = terminals marked '    '.

In all other areas of the EU, as well as new build installations in the UK

after April 2004, the colour codes used are:-
BROWN  = terminals marked 'L'
BLUE = terminals marked 'N'
GREEN / YELLOW = terminals marked '    '

8. Use cable with a maximum outside diameter of 17mm.
9. PVC Cable Entry (see Service Items) must only be used at the bottom cable

entry of the enclosure.

Contents

Page

A

Product Features

2

B

Service Ite  ms

3

C

Safety Instructions

4

Installation

5

E

Testing

14

F

Service Maintenance

14

G

Specification

16

H

Guarantee

17

Please leave this leaflet with the end user for future reference

52.5mm

Centre
Line of
Conduit or
Cable 
Entry

77.5 mm

TOP

Conduit Entry

Entry Blank

Drain Hole

Drill Out Feature

5 mm
Drill Bit

Mounting
Box

50048742:Rev.B  03/03/2011  09:18  Page 1