76
-
'20 • PAC-SM-351
LED
U
V
W
LED1
LED3
LED5
LED2
LED4
LED6
LED1
LED3
LED5
LED2
LED4
LED6
LED1
LED3
LED5
LED2
LED4
LED6
LED1
LED3
LED5
LED2
LED4
LED6
LED1
LED3
LED5
LED2
LED4
LED6
LED1
LED3
LED5
LED2
LED4
LED6
~
(7) Inverter checker for diagnosis of inverter output
Models FDC100, 125, 140VNX-W,100, 125, 140VSX-W
●
Checking method
ON/OFF
status of LED
If all of LED are ON/OFF
according to following pattern
If all of LED stay OFF or
some of LED are ON/OFF
Inverter PCB
Normal
Anomalous
During this period, ON/OFF status of LED is
repeated cyclically according to following pattern
(i) Setup procedure of checker.
1) Power OFF (Turn off the breaker).
2) Remove the terminal cover of compressor and disconnect the wires (U, V, W) from compressor.
3) Connect the wires U (Red) , V (White) and W (Black) of checker to the terminal of disconnected wires (U, V, W)
from compressor respectively.
(ii) Operation for judgment.
1) Power ON after JSW10-4 on outdoor inverter PCB was turned ON.
2) After 15 seconds since power has turned ON, LED start ON/OFF for 5 seconds cyclically and it repeats 10 times.
3) Check ON/OFF status of 6 LED's on the checker.
4) Judge the PCB by ON/OFF status of 6 LED's on the checker.
5) Be sure to turn off JSW10-4 on outdoor inverter PCB, after finishing the check operation.
Power ON or start check operation
1
2
3
10
Cyclically
●
ON
○
OFF
Red
Black
White
Faston terminal
〈
Inverter checker
〉
Connect to the terminal of the wires which are disconnected from compressor.
LED ON/OFF pattern
15 sec.
5sec.
5sec.
5sec.
Summary of Contents for SRK100VNXWPZSX
Page 181: ...180 20 PAC SM 351 1 e SRK series PHA012D402...
Page 182: ...181 20 PAC SM 351 Screw...
Page 183: ...182 20 PAC SM 351 3 PHA012D402...
Page 184: ...183 20 PAC SM 351 4 PHA012D402...