Installation manual for wired remote controller (

RC-E3

)

C

Installation manual for wired remote controller

Installation and wiring of remote controller

Wiring of remote controller should use 0.3mm

2

 × 2 core wires or cables. (on-site configuration)

Maximum prolongation of remote controller wiring is 600 m.

100 - 200m.........................0.5mm

2

 × 2 cores

Under 300m .......................0.75mm

2

 × 2 cores

Under 400m .......................1.25mm

2

 × 2 cores

Under 600m .......................2.0mm

2

 × 2 cores

Master/ slave setting when more than one remote controllers are used

A maximum of two remote controllers can be connected to one indoor unit (or one group of indoor units.)

Remote controller cord (no polarity)

Remote controller

SW1 "Master"

Switch

Setting

Contents

M

Master remote controller

SW1

S

Slave remote controller

The indication when power source is supplied

When power source is turned on, the following is displayed on the remote controller until the   
communication between the remote controller and indoor unit settled.

Master remote controller : "                               "
Slave remote controller : "                               "

At the same time, a mark or a number will be displayed for two seconds first.
This is the software's administration number of the remote controller, not an error cord.

The range of temperature setting

When shipped, the range of set temperature differs depending on the operation mode as below.

Heating : 16~30

o

C (55~86

o

F)

Except heating (cooling, fan, dry, automatic) : 18~30

o

C (62~86

o

F)

Upper limit and lower limit of set temperature can be changed with remote controller.

Upper limit setting: valid during heating operation.  Possible to set in the range of 20 to 30

o

C (68 to 86

o

F).

Lower limit setting: valid except heating (automatic, cooling, fan, dry) Possible to set in the range of 18 to 26

o

C (62 to  

79

o

F).

When you set upper and lower limit by this function, control as below.

1.  When      TEMP RANGE SET, remote controller function of function setting mode is "INDN CHANGE" (factory setting),

During heating, you cannot set the value exceeding the upper limit.

During operation mode except heating, you cannot set the value below the lower limit.

2.  When      TEMP RANGE SET, remote controller function of function setting mode is "NO INDN CHANGE"

During heating, even if the value exceeding the upper limit is set, upper limit value will be sent to the indoor unit.
But, the indication is the same as the temperature set.

During except heating, even if the value lower than the lower limit is set, lower limit value will be sent to the indoor unit.
But, the indication is the same as the temperature set.

How to set upper and lower limit value

1.    Stop the air-conditioner, and press             (SET) and              (MODE) button at the same time for over three  
       seconds .

The indication changes to "FUNCTION SET      ".

2.    Press        button once, and change to the "TEMP RANGE      " indication.
3.    Press             (SET) button, and enter the temperature range setting mode.
4.    Select  "UPPER LIMIT      " or "LOWER LIMIT     " by using               button.
5.    Press            (SET) button to fix.
6.    When "UPPER LIMIT      " is selected (valid during heating)

Press            (SET) button to fix. Indication example: "UPPER 26

O

C" (Displayed for two seconds)

After the fixed upper limit value displayed for two seconds, the indication will return to "UPPER LIMIT      ".

7.    When "LOWER LIMIT      " is selected (valid during cooling, dry, fan, automatic)

Indication: "              SET UP"       "LOWER 18

O

C     "

8.    Press  ON/OFF  button to finish.

PJA012D728A

When remote controller cannot communicate with the indoor unit for half an hour, the below indication will
appear.
Check wiring of the indoor unit and the outdoor unit etc.

Read together with indoor unit's installation manual.

Accessories

Remote controller, wood screw

2 pieces

Prepare on site

Remote controller cord (2 cores) 

[In case of embedding cord] Erectrical box, M4 screw (2 pieces)
[In case of exposing cord] Cord clamp (if needed)

Screw 

Installation procedure

Open the cover of remote controller , and remove the screw under the  
buttons without fail.

Remove the upper case of remote controller.
Insert a flat-blade screwdriver into the dented part of the upper part  
of the remote controller, and wrench slightly.

[In case of embedding cord]

Embed the erectrical box and remote controller cord beforehand.

Prepare two M4 screws (recommended length is 12-16mm) on site, and install the lower case to erectrical box.  
Choose either of the following two positions in fixing it with screws.

Connect the remote controller cord to the terminal block.
Connect the terminal of remote controller (X,Y) with the terminal of  
indoor unit (X,Y). (X and Y are no polarity)

Install the upper case as before so as not to catch up the remote controller cord,  
and tighten with the screws.

[In case of exposing cord]

You can pull out the remote controller cord from left upper part or center upper part.
Cut off the upper thin part of remote controller lower case with a nipper or knife, 
and grind burrs with a file etc.

Install the lower case to the flat wall with attached two wooden screws.

Connect the remote controller cord to the  
terminal block.
Connect the terminal of remote controller (X,Y)  
with the terminal of indoor unit (X,Y).
(X and Y are no polarity)
Wiring route is as shown in the right diagram  
depending on the pulling out direction.

The wiring inside the remote controller case should be within 0.3mm

2

 (recommended) to 0.5mm

2

.

The sheath should be peeled off inside the remote controller case.
The peeling-off length of each wire is as below.

Pulling out from upper left Pulling out from upper center

X wiring : 215mm
Y wiring : 195mm

X wiring : 170mm
Y wiring : 190mm

Install the upper case as before so as not to catch up the remote controller cord, and tighten with  
the screws.
In case of exposing cord, fix the cord on the wall with cord clamp so as not to slack.

In case of pulling out from  

upper left

In case of pulling out from 

upper center

The peeling-off length  

of sheath

WARNING

CAUTION

Fasten the wiring to the terminal securely and hold the cable securely so as not to apply unexpected stress on the 
terminal.
Loose connection or hold will cause abnormal heat generation or fire.

Make sure the power supply is turned off when electric wiring work. 
Otherwise, electric shock, malfunction and improper running may occur. 

DO NOT install the remote controller at the following places in order to avoid malfunction.

DO NOT leave the remote controller without the upper case.

(1) Places exposed to direct sunlight
(2) Places near heat devices
(3) High humidity places

In case the upper cace needs to be detached, protect the remote controller with a packaging box or bag in 
order to keep it away from water and dust.

(4) Hot surface or cold surface enough to generate condensation
(5) Places exposed to oil mist or steam directly
(6) Uneven surface

Tighten the screws after 
cutting off the thin part of 
screw mounting part.

Controller cord

Erectrical box 

(Prepare on site)

Lower part

Lower part

Upper part

Lower case

Lower case

Wiring oulet

Wiring oulet

M4 screw     2 (Prepare on site)

The thin part

Wiring

Wiring

Upper 

Upper 

Sheath

Upper case

Upper case

Board

Board

Lower

Lower

If the prolongation is over 100m, change to the size below.
But, wiring in the remote controller case should be under 0.5mm

2

 . Change the wire size outside 

of the case according to wire connecting. Waterproof treatment is necessary at the wire 
connecting section. Be careful about contact failure.

Remote controller

SW1 "Slave"

Lower

Master

Slave

Upper

Board

The left mark is only an 

example. Other marks may 

appear.

Previous button

Upper part

Lower

Lower case

Upper

Lower

Lower case

Upper 

Sheath

If upper limit value is set

If upper limit value is set

If lower limit value is set

If lower limit value is set

Indication: "              SET UP"       "UPPER 30

O

C     "

Select the upper limit value with temperature setting button             . Indication example: "UPPER 26

O

C        "   

(blinking)

Select the lower limit value with temperature setting button             . Indication example: "LOWER 24

O

C        "  

(blinking)

 Press            (SET) button to fix. Indication for example: "LOWER 24

O

C" (Displayed for two seconds)

After the fixed lower limit value displayed for two seconds, the indication will return to "LOWER LIMIT       ".

It is possible to finish by pressing 
 ON/OFF  button on the way, but 
unfinished change of setting is 
unavailable.
During setting, if you press           
(RESET) button, you return to the 
previous screen.

Indoor units

Set SW1 to "Slave" for the slave remote controller. It was factory set to "Master" for shipment.

Note: The setting "Remote controller thermistor enabled" is only selectable with the master remote 

controller in the position where you want to check room temperature. 
The air conditioner operation follows the last operation of the remote controller regardless of the 
master/ slave setting of it.