10
- 60
10.4 Checking the Error Description with the CC IE Control Network Diagnostics
10.4.9 Control station duplication and own station No. duplication
10
TROUBLESHOOTING
10.4.9
Control station duplication and own station No. duplication
The following explains the procedures to be taken when control station or station No. is
duplicated.
(1) Turning ON all stations simultaneously
Stations other than duplicated control stations do not receive parameters since they
recognize that no control station exists in a network.
Section 10.4.4 Parameter unreceived
POINT
If it is difficult to identify the error cause, perform the CC IE Control Network
Diagnostics after the circuit test.
Figure 10.46 Turning ON all stations simultaneously
Select the own station.
Control station duplication and station No. duplication can be detected.
Change the network type and station No.
Since current control station is not displayed, you can see that no control
station exists.
Control
station
No.1
Normal station
No.2
Control station
No.1
Normal station
No.3
Selected
station