9
DEDICATED INSTRUCTIONS
9.10 JP/GP.RECV
9
- 95
9
DE
DICA
T
E
D
INS
T
RUCT
IONS
10
T
R
OUB
L
E
S
HO
OT
IN
G
APPENDI
CES
INDEX
9.10 JP/GP.RECV
This instruction reads data received from a programmable controller on another station.
(For main program)
(1) Setting data
* 1 Local devices and file registers for each program cannot be used as devices in setting data.
Table 9.52 Devices available for setting data
Setting
data
Available devices
Internal device
(System, User)
File
register
Link direct device
J \
Intelligent function
module device
U \G
Index register
Zn
Constant
Others
Bit
Word
Bit
Word
K, H
$
(S1)
—
—
(D1)
—
—
(D2)
—
Figure 9.77 Instruction format
Table 9.53 Setting data
Setting data
*1
Description
Data type
Jn
Network No. of the own station (1 to 239, 254)
254: The network specified in Valid module during other station access
Binary 16 bits
Un
Start I/O number of the own station's CC-Link IE controller network
module
(00 to FE
H
: The higher two digits of the 3-digit I/O number)
(S1)
Start device of the own station that stores control data
(
Device name
(D1)
Start device of the own station that stores receive data
(A contiguous area for the receive data length is required.)
(D2)
The own station's device that is turned on for one scan upon
completion of the instruction
(D2)+1 also turns ON if the instruction execution has failed.
Bit
JP.RECV
Start contact
[Instruction format]
[Execution condition]
[Instruction symbol]
GP.RECV
Start contact
JP.RECV
Jn
(S1)
(D1)
GP.RECV
Un
(S1)
(D1)
(D2)
(D2)