8.3 Replacing Module in Redundant System
8.3.6 Main Base Unit Replacement Procedure
8
8.3.6 Main Base Unit Replacement Procedure
(1) Main Base Unit Replacement
The control system main base unit cannot be replaced while the redundant system is
running.
In this case, switching its system to the standby system, then replace that main base
unit.
Perform replacement of the standby system's main base unit after turning the standby
system's power supply OFF.
The power supply for the standby system can be turned OFF even when the
redundant system is active.
Diagram 8.32 System where Control System's Main Base Unit Is Replaced
Diagram 8.33 System where Standby System's Main Base Unit Is Replaced
Control system
Standby system
Tracking cable
Replace after using GX Developer to
switch over to the standby system.
Main base unit
GX Developer
Control system
Standby system
Tracking cable
Main base unit
Replace after turning OFF the
standby system power.
GX Developer