8.3 Replacing Module in Redundant System
8.3.1 CPU Module Replacement
8
POINT
When the standby system is powered OFF, the control system CPU module
develops STANDBY SYS.DOWN (error code: 6300) continuation error.
After the replacement of the standby system CPU module is complete, clear the
error in the control system CPU module as necessary.
Refer to Section 8.2 for the error resetting method.
Disconnecting the Tracking Cable
Disconnect the tracking cable from the standby system CPU module.
Refer to Section 3.3, for disconnecting the tracking cable.
Replacing the Standby System CPU Module
1)
Remove the standby system CPU module from the main base unit.
2)
Mount an alternative CPU module (the same model as the control system CPU module) to the
main base unit.
3)
Connect the CPU module battery connector to the battery connector pin.
Refer to the QCPU User's Manual (Hardware Design, Maintenance and Inspection), for
removing/mounting the CPU module and battery connection.
Connecting the Tracking Cable
Connect the tracking cable connector to the standby system CPU module.
Refer to Section 3.3, for connecting the tracking cable.
Power ON the Standby System
1)
Set the RUN/STOP switch of the standby system CPU module to the STOP position.
2)
Set the RESET/L.CLR switch of the standby system CPU module to the central position (reset
switch neutral position).
3)
Power on the standby system.
Confirming the POWER LED of the Power Supply Module
Confirm that the POWER LED of the power supply module is ON (lit green) and the module is
being properly powered
Executing the Memory Copy from Control System to Standby System
Perform the memory copy from control system to standby system using the GX Developer
connected to the control system CPU module, and write the memory content from the control
system CPU module to the standby system CPU module.
Resetting the Standby System CPU Module
Set the RESET/L.CLR switch of the standby system CPU module to the RESET position.
Setting the Switch of the Standby System CPU Module to That of the Control System
Set the RUN/STOP switch of the standby system CPU module to the same position of that of the
control system CPU module.
Setting the Reset Switch of the Standby System CPU Module to Neutral Position
Set the RESET/L.CLR switch of the standby system CPU module from the RESET position to the
central position (reset switch neutral position).
Diagram 8.21 CPU Module Replacement Procedure
Start standby system