8.1 Troubleshooting Flow
8.1.7 When "TRK. INIT. ERROR (error code: 6140)" Occurred at Redundant System Startup
8
TROUBLESHOOTING
8.1.7 When "TRK. INIT. ERROR (error code: 6140)" Occurred at Redundant
System Startup
(1) "TRK. INIT. ERROR" occurrence conditions
(a) This error occurs when either of the following operations is performed
during starting the redundant system and before the
"
BACKUP
"
LED turns
green.
• Either system was powered off.
• The CPU module in either system was reset.
(b) This error may occur in the system using the redundant type extension base
unit if extension cables are not connected and the system is not powered on
as the procedures shown in Chapter 4.
(2) Corrective action for "TRK. INIT. ERROR"
If "TRK. INIT. ERROR" has occurred during a startup of the redundant system, restart
the system by performing either of the following operations.
(a) Power on System A and System B again
1) When System A/System B has been powered off, power on System A and
System B again simultaneously.
2) The System A CPU module starts as a control system and the System B CPU
module as a standby system.
(b) Set the RESET switches of System A and System B CPU modules to the
neutral position simultaneously
1) When the System A/System B CPU module has been reset, reset the System
A and System B CPU modules and then set their RESET switches to the
neutral position simultaneously.
2) The System A CPU module starts as a control system and the System B CPU
module as a standby system.