73
SW2 setting
Display detail
Explanation for display
Unit
1
ON
2 3 4 5 6
Pulse
LEV-A opening pulse on error occurring
0 to 480
0 to 480
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 130 pulse;
0.5 s 0.5 s 2 s
:
Indoor room temperature (TH1) on error
occurring
8 to 39
8 to 39
:
Indoor pipe temperature/Liquid (TH2) on
error occurring
−39 to 88
−39 to 88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(Example) When −15°C;
0.5 s 0.5 s 2 s
Pressure saturation temperature (T
63HS
)
on error occurring
−39 to 88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(Example) When −15°C;
0.5 s 0.5 s 2 s
2-phase pipe (TH6) on error occurring
−39 to 88
−39 to 88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(Example) When −15°C;
0.5 s 0.5 s 2 s
Ambient temperature (TH7) on error
occurring
−39 to 88
−39 to 88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(Example) When −15°C;
0.5 s 0.5 s 2 s
Outdoor heat sink temperature (TH8) on
error occurring
−40 to 200
−40 to 200
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
30
1
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
15
15
15
15
:
:
:
:
The black square ( ) indicates a switch position.
OCH533D