Main functions of LED (when both No. 1 and 2 of
€
SW3
are ¨OFF¨)
NOTES :If the operation stops to function of the protection device, the check display flashes.
How to use SW1 and 2
●
Pressing
€
SW1
erases the past check contents loaded on the micro-
computer.
●
The output display (light) remains during operation but pressing
€
SW2
displays the past check contents in flashing mode. Pressing the
switch again returns to output display (light).
●
The connector marked s
—
⁄
ı
— is to turn the compressor ON-OFF during servicing.
The compressor stops by disconnecting the white connector as shown at the right.
●
Since LD8 lights when normal power is turned "ON", check the power supply with
the "ON" or "OFF" LD8.
❈
Since the indoor transformer (T) is connected with 230V power, if 208V power is
used, change the wiring connection in the following Procedure.
●
Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1, 2) for indoor and outdoor units.
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
CAUTION FOR POWER SUPPLY WIRING
CAUTION FOR SERVICING
FROM INDOOR UNIT
CONNECTING WIRES
12V DC (polar)
POWER SUPPLY
208/230V
1phase 60Hz
1
2
TB3
L1
L2
GR
TB1
O.B
LED
TH3
YLW
BRN
11.5V AC
RED
RED
WHT
WHT
WHT
RED
R
R
S
C
T
C
U
52C
MC
51C
W
GRN
WHT
BLU
BLU
WHT
1
2
RED
WHT
RED
ORN
GRY
GRY
WHT
WHT
BLU
YLM
YLM
YLM
YLM
RED
RED
BLU
BLU
WHT
BLU
RED
ORN
15.5V AC
208V
230V
T
ORN
SW1
SW2
SW3
CN3
CN2
TRF
52C
52C
CH
ZNR
FC
C3
MF3
26C
51CM
63H2
63H2
MF3
R/1
F3
S/2
T/3
CH
X12
X12
X11
X11
CN6T
OFF
ON
2
2
1
1
1
S
A
B
5
2
3
4
4
LD8
LD7
LD6
LD5
LD4
LD3
LD2
LD1
5
6
ORN
36.0V AC
MODELS : PU18EK
SYMBOL
C
NAME
COMPRESSOR CAPACITOR
C3
FAN CAPACITOR
CH
CRANKCASE HEATER
CN3<O. B>
CONNECTING WIRES INDOOR/OUTDOOR
CONNECTOR
CN6T<O. B>
TRANSFORMER CONNECTOR
SYMBOL
LD1 ~ LD8
NAME
LED <CHECK, SERVICE>
MC
COMPRESSOR
MF3
OUTDOOR FAN MOTOR (INNER THERMOSTAT)
O. B
OUTDOOR CONTROLLER BOARD
SW1, 2, 3<O. B> SELECT SWITCH <CHECK, SERVICE>
T
TRANSFORMER
FC <O. B>
FAN CONTROLLER
F3 <O. B>
FUSE <6A>
SYMBOL
TH3
NAME
OUTDOOR COIL THERMISTOR
X11 <O. B>
CRANKCASE HEATER RELAY
X12 <O. B>
COMPRESSOR RELAY
ZNR <O. B>
VARISTOR
52C
CONTACTOR
63H2
HIGH PRESSURE SWITCH <PROTECT>
TB1
POWER SUPPLY TERMINAL BLOCK
TB3
CONNECTING WIRES INDOOR/OUTDOOR
TERMINAL BLOCK
51C
OVERCURRENT RELAY
LED NO.
Output display (light)
Check display (flush)
LD1
Compressor indoor command
—
LD2
—
—
LD3
—
Pipe temperature sensor short / open
LD4
Compressor ON
63H2 functions
LD5
Outdoor fan ON
—
LD6
—
—
LD7
—
TH3 overheat protection
LD8
Crankcase heater ON
Defective input
White connector
When power Supply is 208V
RED
WHITE
208V
ORANGE
230V