264
(11)Remote registers (RWw16 to RWw17, RWw2E to RWw2F)
Address
(RWw)
Item
Description
Default
CH1 CH2
16
2E
Time unit setting
(Sampling
counter/Periodic pulse
counter)
• Set a unit of time for the sampling counter function or the periodic pulse
counter function.
• The following shows the setting range.
0: 1ms
1: 10ms
• The reflection timing of the setting value
1)
When Initial data processing request flag (RX8) turns off
2)
When Initial data setting request flag (RY9) is turned off then on (only while
Initial data processing request flag (RX8) is off)
3)
When CH
Setting change request (Sampling counter/Periodic pulse
counter) (RY27, RY3F) is turned off then on
0
17
2F
Cycle setting
(Sampling
counter/Periodic pulse
counter)
• Set the sampling period for the sampling counter function or the cycle time of
the periodic pulse counter function.
• The following shows the setting range.
1 to 65535
(When CH
Time unit setting (Sampling counter/Periodic pulse counter)
(RWw16, RWw2E) is set to 1ms (0), the sampling period or the cycle time is
indicated in increments of 1ms and when set to 10ms (1), in increments of
10ms.)
• The reflection timing of the setting value
1)
When Initial data processing request flag (RX8) turns off
2)
When Initial data setting request flag (RY9) is turned off then on (only while
Initial data processing request flag (RX8) is off)
3)
When CH
Setting change request (Sampling counter/Periodic pulse
counter) (RY27, RY3F) is turned off then on
0