(6) Remote registers (RWr21 to RWr23, RWr39 to RWr3B)
Address
(RWr)
Item
Description
Default
CH1 CH2
21
39
External input status
• This area stores the input statuses of phase Z, the function, the latch counter,
phase A, and phase B of the external I/O connector.
• When CH
Operation mode setting (address:0120
H
, 0140
H
) is set to either of
Frequency Measurement Mode (1), Rotation Speed Measurement Mode (2),
or PWM Output Mode (4), Function input status (RWr21.b1, RWr39.b1) is
always OFF (0).
• With Negative Logic (1) being set in CH
Function input logic setting
(address: 0127
H
, 0147
H
) or CH
Latch counter input logic setting (address:
0128
H
, 0148
H
), its input status changes to OFF (0) when a voltage is applied.
• When Initial data setting request flag (RY9) is turned off then on, the value in
this area is cleared.
0000
H
22
3A
Latest error code
• This area stores the latest error code of the generated major error or
moderate error.
• When multiple errors in the same category occur, this area stores the error
code of the later error.
• When a moderate error occurs while a major error is occurring, this area does
not store the error code of the moderate error.
• For the error code, refer to Page 208, Section 11.2.
0000
H
23
3B
Latest warning code
• This area stores the error code of the generated minor error.
• When multiple minor errors occur, this area stores the error code of the later
error.
• For the error code, refer to Page 208, Section 11.2.
0000
H
0
0
0
0
0
0
0
0
0
0
0
0 (fixed)
b15
b0
b1
b2
b3
b4
b5
b6
b7
b8
b9
b10
b11
b12
b13
b14
Phase Z input
status
0: OFF
1: ON
Function input
status
0: OFF
1: ON
Latch counter
input status
0: OFF
1: ON
Phase B input
status
0: OFF
1: ON
Phase A input
status
0: OFF
1: ON
Summary of Contents for NZ2GFCF-D62PD2