223
CHAPTER 11 TROUBLESHOOTING
11
11.2 Er
ror
Code List
(2) Error code list (D000
H
to DFFF
H
(D529
H
and D52B
H
excluded))
When an error occurs, the ERR. LED does not turn on. The D LINK LED flashes or turns off.
Troubleshoot the problem with the CC-Link IE Field Network diagnostics. (
When multiple errors occur, only the latest error code is stored in CH
Latest error code (RWr22, RWr3A) or CH
Latest
warning code (RWr23, RWr3B).
Old errors can be checked with the error history of GX Works2.
For the error history, refer to the following.
• Checking by executing a command of the slave station (
• Error history 1 to 15 (address: 0A00
H
to 0AFF
H
) (
Error code
(hexadecimal)
Error name
Description and cause
Action
D0E0
H
Station type
mismatch
The network parameter is
incorrect or outside the range.
In the network configuration settings of the master station, change
the station type to the remote device station.
D0E1
H
Own station
reserved
The network parameter is
incorrect or outside the range.
• In the network configuration settings of the master station, cancel
the reserved station setting.
• Change the station number of the module to a station number that
is not reserved.
D0E2
H
Station No.
already in use
(own station)
The network parameter is
incorrect or outside the range.
• Set a unique station number.
• After taking the above action, turn off then on or reset all the
stations where this error has been detected.
D0E3
H
Own station
No. out of
range
The network parameter is
incorrect or outside the range.
Add the station information of the module in the network
configuration settings of the master station.
D217
H
Transient data
command
error
The transient data request
command is incorrect.
Correct the request command at the request source, and retry the
operation.
D2A0
H
Receive buffer
full
The target station is
overloaded and cannot
receive transient data.
• Check the network status using the CC-Link IE Field Network
diagnostics of GX Works2.
• When the target station is overloaded and cannot receive transient
data, send the data to the target station after a while.
D2A3
H
Transient data
length error
The received transient data is
incorrect.
Correct the number of data (frame length) at the request source, and
retry the operation.
D72A
H
Station
number switch
out of range (a
value other
than 1 to 120)
A station number out of range
has been set.
Set the station number within the allowable range.
DF01
H
Transient data
divided error
The divided transient data
have been received.
Set the transient data size within the range that can be handled by
the module. Then send the transient data that is not divided.