160
8.16
PWM Output Function
The PWM output function outputs the PWM waveform (up to 200kHz) from one of the coincidence output 1 to 4
terminals (EQU1 to EQU4). Up to four points can be assigned for one channel. The same waveform is to be output to
the assigned terminals. The ON width setting (PWM output) can be changed during PWM output.
(1) Setting method of the PWM output function
1.
Set "Parameter write" for "Method selection".
"CC IE Field Configuration" window
Select a high-speed counter module in "List of stations"
[CC IE Field Configuration]
[Parameter Processing of Slave Station]
2.
Set "CH
Operation mode setting" to "4: PWM Output Mode".
EQU1 to
EQU4 terminal
Pulse output
High-speed
counter module
Remote register
PWM cycle: 5 s to 1s
CH PWM output assignment setting
(RWw1D, RWw35)
CH ON width setting (PWM output)
(RWw1E to RWw1F, RWw36 to RWw37)
CH ON width setting change request
(PWM output) (RY35, RY4D)
CH Cycle setting (PWM output)
(RWw20 to RWw21, RWw38 to RWw39)
Remote output signal
CH PWM output start command
(RY26, RY3E)
PWM output
function