114
8.3.3
Preset/replace (at coincidence output) function
The preset/replace (at coincidence output) function performs the preset/replace function (replaces the present value
with a value preset by the user) at the rising state (off to on) of Coincidence output 1 and 2.
The preset/replace by this function is performed to the channel assigned to Coincidence output 1 and 2.
This function is not available for Coincidence output 3 and 4.
(1) Setting method of the preset/replace (at coincidence output) function
1.
Set "Parameter write" for "Method selection".
"CC IE Field Configuration" window
Select a high-speed counter module in "List of stations"
[CC IE Field Configuration]
[Parameter Processing of Slave Station]
2.
Set "0: Coincidence Output Function" for "Comparison output setting".
3.
Set a channel to be compared for "Coincidence output 1 to 4 channel assignment setting".
4.
Set the comparison condition for "Coincidence output 1 to 4 comparison condition setting".
5.
Set "1: Present value replaced" for "Preset/replace setting at coincidence output (Coincidence
output 1 to 2)".