This chapter describes the setting procedures of the D/A converter module.
7.1
Parameter Setting
Set the parameter of this module with the network parameter written to the CPU module of the master station. When
the setting in GX Works2 and the parameter written to the CPU module do not match, the parameter cannot be written
and read. For the setting procedure of the master station, refer to the following.
User's manual for the master/local module used
Write and read the parameter setting of this module with the CPU module in the STOP status.
(Writing and reading are unavailable in the RUN status.)
Remark
●
When points less than the ones of the D/A converter module and extension module are set for the remote I/O signal and
remote register, no error occurs. The cyclic transmission is performed for the data of the points set from the start.
●
When using the D/A converter module, always enable the block data assurance per station. When it is disabled, correct
operation of the D/A converter module cannot be guaranteed.
For the block data assurance per station, refer to the following.
User's manual for the master/local module used
●
Do not set the parameter using the CCPASET instruction in the master station. Correct operation of the D/A converter
module cannot be guaranteed because the module operates with the block data assurance per station disabled when the
CCPASET instruction is executed.
Do not uncheck the box.