7 OPERATION EXAMPLES
7.2 Program Examples
55
7
Auto tuning
Perform auto tuning.
[Tool]
[Module Tool List]
1.
Select "Temperature trace" of "Temperature
Control Module" and click the [OK] button.
2.
Select the module to configure the temperature
control setting and click the [OK] button.
3.
Select "Monitor data write" from the following.
[Setting]
[Monitor data write]
4.
Set "Setting/Operation mode command" to
"1:Operation mode command".
5.
Set "Auto tuning command" to "1:ON".
6.
Then, "Auto tuning status" is set to "Executing",
and auto tuning is started.
7.
When auto tuning is completed, "Auto tuning
status" is set to "Stopped".
8.
Temperature control is performed by set PID
constants.