90
6 WIRING
6.5 Input Wiring
When a CPU module common to sink and source inputs is used
■
Sink input wiring
*1 The grounding resistance should be 100
Ω
or less.
*2 Handle the power supply circuit properly in accordance with "Power Supply Wiring".
*3 For an input device having a parallel resistance or a two-wire proximity switch, a bleeder resistance may be required.
FX5UC-32MT/DSS
FX5-C32EX/DS
COM0
X0
X1
COM0
X0
X1
24 V DC
FX5-16EX/ES
S/S
*1
*2
*3
Fuse
X0
X1
FX5-CNV-IFC
Power
connector
3-wire
sensor
2-wire
sensor
Input
connector
Input
impedance
Input
connector
Input
terminal
Class D
grounding
Summary of Contents for MELSEC iQ-F FX5UC
Page 1: ...MELSEC iQ F FX5UC User s Manual Hardware ...