4 SYSTEM CONFIGURATION
4.3 Limitation on the Number of Input/Output Points
47
4
4.3
Limitation on the Number of Input/Output Points
With the FX5UC CPU modules, a total of 512 points including the number of input/output points of extension devices (max.
256 points) and the number of remote I/O points (max. 384 points) can be controlled.
*1 A bus conversion module is required when using the FX3U-16CCL-M.
*2 A bus conversion module is required when using the FX3U-128ASL-M.
Total number of I/O points and remote I/O points
With the FX5UC CPU module, a total of 512 points or less including the number of input/output points of extension devices
and number of remote I/O points can be controlled.
The total number of I/O points and remote I/O points must not exceed 512 points.
Calculation of the number of input/output points
The number of input/output points is a total of the number of input/output points of the CPU module, I/O module, and the
number of occupied input/output points of intelligent function modules.
The total number of input/output points must not exceed 256 points.
1. Number of input/output points
(including input/output occupied points)
Up to 256 points
CPU
module
I/O
module
Expansion
adapter
Connector
conversion
module
• CC-Link master
*1
• AnyWireASLINK master
*2
CC-Link/AnyWireASLINK system
CC-Link IE field network Basic system
2. Number of remote I/O points
Up to 384 points
Remote I/O station Remote I/O station
Remote I/O station Remote I/O station
Number of input/output points on whole system
Up to 512 points
FX5
Intelligent
module
FX5
Intelligent
module
512 points
+
Number of remote I/O points
(2)
points
Total number of remote I/O which is
obtained in the next subsection
Number of input/output points
(1)
points
The total number of inputs and
outputs which is obtained in the
next subsection
Maximum number of points
controllable on system
Number of input/output
points on whole system
Maximum number of
input/output points
256 points
Number of input/output points
on CPU module and I/O module
+
(A)
+
(B)
Number of occupied
input/output points
(C) modules
8 points
=
Number of
input/output points
(1)
Total number of input/output points of CPU
module and I/O module
(A): Number of input/output points of CPU module (B): Number of input/output points of I/O module
The intelligent module and bus
conversion module occupy 8
input/output points/device.
(C): Number of intelligent function modules and bus conversion modules