APPX
Appendix 3 Precautions for operating ambient temperature
139
A
Appendix 3
Precautions for operating ambient
temperature
This section describes precautions when the device is used at an operating ambient temperature below 0
.
Precaution when used at an operating ambient temperature below 0
• With some exceptions, the operating ambient temperature is -20 to 55
for the FX5 PLCs manufactured in June 2016
onwards.
• The operating ambient temperature is 0 to 55
for the FX5 PLCs manufactured before June 2016.
• When the device is used in a low-temperature environment, use care not to let the product freeze or condensation to occur.
• When used in a low-temperature environment, use in an environment with no sudden temperature changes. If there are
sudden temperature changes because of opening/closing of the control panel or other reasons, condensation may occur,
which may cause a fire, fault, or malfunction. Furthermore, use an air conditioner in dehumidifier mode to prevent
condensation.
Related devices which cannot be used at an operating ambient temperature below 0
The following devices cannot be used at an operating ambient temperature below 0
.
Specifications when used at an operating ambient temperature below 0
For using the device at an operating ambient temperature below 0
, specifications are different from when used at an
operating ambient temperature of 0 to 55
.
Device name
FX5-40SSC-S
FX5-80SSC-S
FX5-CNV-BUS
FX5-CNV-BUSC
Battery (FX3U-32BL)
SD memory card (NZ1MEM-2GBSD, NZ1MEM-4GBSD, NZ1MEM-8GBSD, NZ1MEM-16GBSD, L1MEM-2GBSD, L1MEM-4GBSD)
FX3 expansion module
Terminal module
Input/output cable (FX-16E-500CAB-S, FX-16E-
CAB, FX-16E-
CAB-R)
Item
When used at 0 to 55
When used at below 0
Analog accuracy of FX5-4AD-ADP
Analog input
Within
±
0.2% (
±
32 digit)
Within
±
0.3% (
±
48 digit)