17 ARITHMETIC OPERATION FUNCTIONS
17.3 Subtraction
781
17
17.3
Subtraction
SUB(_E)
These functions output the difference of input values ((s1) - (s2)).
Setting data
■
Descriptions, types, and data types
Processing details
■
Operation processing
• These functions subtract the INT, DINT, or REAL type data input to (s1) and (s2) ((s1)-(s2)), and output the operation result
from (d) in the same data type as (s).
Ex.
Data type is INT
• A value input to (s1) and (s2) is the INT, DINT, or REAL type data value.
• If an underflow and an overflow occur in the operation result, the result will be output as follows from (d).
• When the operation result is 0, the zero flag (SM8020) turns on.
Ladder diagram
Structured text
[Without EN/ENO]
[With EN/ENO]
[Without EN/ENO]
d:=SUB(s1,s2);
[With EN/ENO]
d:=SUB_E(EN,ENO,s1,s2);
Argument
Description
Type
Data type
EN
Execution condition (TRUE: Execution, FALSE: Stop)
Input variable
BOOL
s1, s2
Input
Input variable
ANY_NUM
ENO
Output status (TRUE: Normal, FALSE: Abnormal)
Output variable
BOOL
d
Output
Output variable
ANY_NUM
Data type is INT
Data type is DINT
Data type is REAL
• Even if underflow or overflow occurs in the
operation result, it is not regarded as an
operation error. "SUB_E" outputs "TRUE" from
ENO.
[Example 1]
32767-(-2)=1
(7FFFH)-(0002H)=(0001H)
The most significant bit becomes 1, and the carry
flags (SM716 and SM8022) turn on.
[Example 2]
-32768-2=-1
(8000H)-(0002H)=(FFFFH)
The most significant bit becomes 0, and the borrow
flag (SM8021) turns on.
• Even if underflow or overflow occurs in the
operation result, it is not regarded as an
operation error. "SUB_E" outputs "TRUE" from
ENO.
[Example 1]
2147483647-(-2)=-2147483647
(7FFFFFFFH)-(FFFEH)=(80000001H)
The most significant bit becomes 1, and a negative
value is output.
[Example 2]
-2147483648-2=2147483646
(80000000H)-(0002H)=(7FFFFFFEH)
The most significant bit becomes 0, and a positive
value is output.
An operation error occurs and an undefined value
is output.
s1
d
s2
EN
ENO
d
s1
s2
INT
12345
-
INT
6789
INT
5556
(s1)
(s2)
(d)
Summary of Contents for MELSEC iQ-F FX5 series
Page 1: ...MELSEC iQ F FX5 Series Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 21: ...19 PART 1 PART 1 OVERVIEW Part 1 consists of the following chapter 1 OVERVIEW ...
Page 98: ...96 4 STANDARD FUNCTIONS FUNCTION BLOCKS 4 2 Standard Function Blocks MEMO ...
Page 840: ...838 23 TIME DATA FUNCTIONS 23 4 Division MEMO ...
Page 887: ......