268
6 BASIC INSTRUCTIONS
6.5 Data Conversion Instructions
Converting Gray code to 16-bit binary data
GBIN(P)(_U)
These instructions convert the 16-bit binary gray code data in the device specified by (s) to 16-bit binary data, and store the
converted data in the device specified by (d).
Setting data
■
Descriptions, ranges, and data types
■
Applicable devices
Processing details
• These instructions convert the 16-bit binary gray code data in the device specified by (s) to 16-bit binary data, and store the
converted data in the device specified by (d).
Precautions
When an input relay (X) is specified as (s), the response delay will be "Scan time of CPU Input filter constant".
Operation error
There is no operation error.
Ladder diagram
Structured text
ENO:=GBIN(EN,s,d);
ENO:=GBINP(EN,s,d);
ENO:=GBIN_U(EN,s,d);
ENO:=GBINP_U(EN,s,d);
Operand
Description
Range
Data type
Data type (label)
(s)
GBIN(P)
Gray code data or head device storing the gray
code data
0 to 32767
16-bit signed binary
ANY16_S
GBIN(P)_U
0 to 65535
16-bit unsigned binary
ANY16_U
(d)
GBIN(P)
Head device for storing the binary data after
conversion
16-bit signed binary
ANY16_S
GBIN(P)_U
16-bit unsigned binary
ANY16_U
Operand
Bit
Word
Double word
Indirect
specification
Constant
Others
X, Y, M, L,
SM, F, B, SB
U
\G
T, ST,
C, LC
T, ST, C, D,
W, SD, SW, R
U
\G
Z
LC
LZ
K, H
E
$
(s)
(d)
(s)
(d)
(d) BIN
(s)
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
1
1
1234
1234
b15
b15
b0
b0
···
···
Gray code
16 bits
Summary of Contents for MELSEC iQ-F FX5 series
Page 1: ...MELSEC iQ F FX5 Series Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 21: ...19 PART 1 PART 1 OVERVIEW Part 1 consists of the following chapter 1 OVERVIEW ...
Page 98: ...96 4 STANDARD FUNCTIONS FUNCTION BLOCKS 4 2 Standard Function Blocks MEMO ...
Page 840: ...838 23 TIME DATA FUNCTIONS 23 4 Division MEMO ...
Page 887: ......