6 BASIC INSTRUCTIONS
6.2 Arithmetic Operation Instructions
161
6
6.2
Arithmetic Operation Instructions
Adding 16-bit binary data
+(P)(_U) instruction and ADD(P)(_U) instruction can be used for addition of 16-bit binary data.
+(P)(_U) [using two operands]
These instructions add the 16-bit binary data in the device specified by (d) and the 16-bit binary data in the device specified by
(s), and store the result in the device specified by (d).
Setting data
■
Descriptions, ranges, and data types
■
Applicable devices
Processing details
• These instructions add the 16-bit binary data in the device specified by (s) to the 16-bit binary data in the device specified
by (d), and store the addition result in the device specified by (d).
• When underflow or overflow occurs in the operation result, the following processing is executed. In this case, the carry flag
(SM700, SM8022) does not turn ON.
Operation error
There is no operation error.
Ladder diagram
Structured text
Not supported
Operand
Description
Range
Data type
Data type (label)
(s)
+(P)
Addend data or the device where the data that
is added to another is stored
-32768 to +32767
16-bit signed binary
ANY16_S
+(P)_U
0 to 65535
16-bit unsigned binary
ANY16_U
(d)
+(P)
Device where the data to which another is
added is stored
-32768 to +32767
16-bit signed binary
ANY16_S
+(P)_U
0 to 65535
16-bit unsigned binary
ANY16_U
Operand
Bit
Word
Double word
Indirect
specification
Constant
Others
X, Y, M, L,
SM, F, B, SB
U
\G
T, ST,
C, LC
T, ST, C, D,
W, SD, SW, R
U
\G
Z
LC
LZ
K, H
E
$
(s)
(d)
(s)
(d)
b15
b0
5678 (BIN)
(d)
(s)
(d)
1234 (BIN)
6912 (BIN)
+
···
b15
b0
···
b15
b0
···
+
→
+
→
+
→
K-32768
K-2
K32766
K65535
K2
K1
K32767
K2
K-32767
(FFFFH)
(0002H)
(0001H)
(7FFFH)
(0002H)
(8001H)
(FFFEH)
(7FFEH)
(8000H)
In case of +(P)
Because the highest bit is 1, the value is negative.
In case of +(P)(_U)
Because the highest bit is 0, the value is positive.
Summary of Contents for MELSEC iQ-F FX5 series
Page 1: ...MELSEC iQ F FX5 Series Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 21: ...19 PART 1 PART 1 OVERVIEW Part 1 consists of the following chapter 1 OVERVIEW ...
Page 98: ...96 4 STANDARD FUNCTIONS FUNCTION BLOCKS 4 2 Standard Function Blocks MEMO ...
Page 840: ...838 23 TIME DATA FUNCTIONS 23 4 Division MEMO ...
Page 887: ......