5 SEQUENCE INSTRUCTIONS
5.7 Stop Instruction
143
5
5.7
Stop Instruction
Stopping the sequence program
STOP
This instruction resets outputs (Y) and stops operation of the CPU module when the execution command turns ON. (This
operation is the same as setting the switch to STOP.)
Processing details
• This instruction resets outputs (Y) and stops operation of the CPU module when the execution command turns ON. (This
operation is the same as setting the switch to STOP.)
• To restart operation of the CPU module after this instruction is executed, return the switch from RUN
STOP and set it to
RUN again.
Operation error
Ladder diagram
Structured text
ENO:=STOP(EN);
Error code
(SD0/SD8067)
Remarks
3340
The STOP instruction is executed before the NEXT instruction is executed after the FOR instruction is executed.
3381
The STOP instruction is executed before the RET instruction is executed after the CALL(P) or XCALL(P) instruction is executed.
3582
The STOP instruction is executed before the IRET instruction is executed in the interruption program.