18
(7) CC-Link/LT module
To supply the CL2DA2-B and CL2AD4-B with 24VDC power using
the CL1PAD1, keep the length of the power cable from the
CL1PAD1 to the 24VDC power supply to 30m or less.
(8) Measures against static electricity
When using an insulation displacement connector without
connector cover, a connected cable for the connector is thin in
applicable wire size and coating. Therefore, note that the module
may cause an electric discharge failure.
As measures against the failure, using pressure-displacement type
connector whose applicable wire size is thick or soldering type
connector is recommended.
3.1.4 Power supply module
The precautions required for each power supply module are described
below. Always observe the items noted as precautions.
*1
Filter attachment to the power cable is not required for the A1S63P product
with the version (F) and later. However, use the 24VDC panel power
equipment that conforms to the CE.
*2
Make sure to attach two ferrite cores to the power line.
Attach them as close to the power supply module as possible.
Use a ferrite core whose damping characteristic is equivalent to that of the
RFC-H13 produced by KITAGAWA INDUSTREIS CO., LTD.
Model
Precautions
A1S61PN, A1S62PN
Make sure to short the LG and FG terminals with a cable of
6 to 7cm and ground the cable.
A1S63P *1
Use the 24VDC panel power equipment conforming to the
EU Directive.
A1SJHCPU(S8)
Make sure to short and ground the LG and FG terminals.*2