290
(4) PLC RAS Setting
Parameters required for performing the RAS functions are set.
(To the next page)
Item
Parameter
No.
Description
Setting range
Default
Reference
WDT (Watchdog
Timer) Setting
WDT Setting
3000
H
Set a watchdog timer value.
10ms to 2000ms
(In increments of
10ms)
200ms
Initial Execution
Monitoring Time
Set a watchdog timer value for
using an initial execution type
program.
10ms to 2000ms
(In increments of
10ms)
⎯
Error Check
3001
H
Whether to check the following
errors can be selected.
• Carry Out Battery Check
• Check Device Range at
Indexing
Selected/
deselected
Selected
Operating Mode When There is an Error
3002
H
Set the operation mode of the
CPU module when the following
errors are detected.
• Computation Error
• Intelligent Module Program
Execution Error
• File Access Error
• Memory Card Operation Error
Stop/Continue
Stop