14 - 12
14. CONNECTION TO SIEMENS PLC
14.3 Ethernet Connection
GOT Ethernet setting
Ethernet setting
(1) Ethernet connection type: FETCH/WRITE
This section describes the Ethernet setting for the
communication driver SIEMENS S7 (Ethernet).
Item
Description
Range
GOT IP Address
Set the IP address of the GOT.
(Default: 192.168.0.18)
0.0.0.0 to
255.255.255.255
Subnet Mask
Set the subnet mask for the sub
network. (Only for connection via
router)
If the sub network is not used, the
default value is set.
(Default: 255.255.255.0)
0.0.0.0 to
255.255.255.255
Default
Gateway
Set the router address of the default
gateway where the GOT is
connected. (Only for connection via
router)
(Default: 0.0.0.0)
0.0.0.0 to
255.255.255.255
周辺 S/W 通信
用ポート No.
Set the GOT port No. for the S/W
communication.
(Default: 5015)
1024 to 5010,
5014 to 65534
(Except for 5011,
5012, 5013, and
49153)
トランスペアレ
ント用ポート
No.
Set the GOT port No. for the
transparent function.
(Default: 5014)
1024 to 5010,
5014 to 65534
(Except for 5011,
5012, 5013, and
49153)
Item
Description
Set value
Host
The host is displayed. (The host is
indicated with an asterisk (*).)
―
Net No.
Set the network No. of the
connected Ethernet module.
(Default: blank)
1 to 239
Station
Set the station No. of the connected
Ethernet module.
(Default: blank)
1 to 64
Type
SIEMENS S7 (fixed)
SIEMENS S7
(fixed)
IP Address
Set the IP address of the connected
Ethernet module.
(Default: blank)
PLC side IP
address
FETCH Port
No.
Set the FETCH port No. of the
connected Ethernet module.
(Default: 2000)
1024 to 65534
WRITE Port No.
For the WRITE port No. of the
connected Ethernet module, the
value that the FETCH port No. is
incremented by one is set
automatically.
(Default: 2001)
1025 to 65535
Communication TCP (fixed)
TCP (fixed)
Summary of Contents for GOT2000Series
Page 2: ......
Page 17: ...A 15 REVISIONS WARRANTY...
Page 52: ...1 30 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring...
Page 54: ......
Page 78: ...3 10 3 CONNECTION TO HITACHI PLC 3 6 Device Range that Can Be Set...
Page 100: ...4 22 4 CONNECTION TO FUJI PLC 4 7 Precautions...
Page 174: ...7 24 7 CONNECTION TO YOKOGAWA PLC 7 4 Device Range that Can Be Set...
Page 262: ...9 54 9 CONNECTION TO RKC TEMPERATURE CONTROLLER 9 7 Precautions...
Page 280: ...10 18 10 CONNECTION TO ALLEN BRADLEY PLC 10 4 Device Range that Can Be Set...
Page 296: ...11 16 11 CONNECTION TO GE PLC 11 7 Precautions...
Page 308: ...12 12 12 CONNECTION TO LS INDUSTRIAL SYSTEMS PLC 12 6 Device Range that Can Be Set...
Page 332: ...14 18 14 CONNECTION TO SIEMENS PLC 14 4 Device Range that Can Be Set...
Page 334: ...REVISIONS 2...
Page 337: ......