![Mitsubishi GOT2000Series Connection Manual Download Page 269](http://html1.mh-extra.com/html/mitsubishi/got2000series/got2000series_connection-manual_1809187269.webp)
10. CONNECTION TO ALLEN-BRADLEY PLC
10.2 Serial Connection
10 - 7
CONNECTION T
O
ALLEN-BRA
DLEY PLC
10
10.2.4
Connection Diagram
The following diagram shows the connection between the
GOT and the PLC.
RS-232 cable
(1) Connection diagram
(2) Precautions when preparing a cable
(a) Cable length
The length of the RS-232 cable must be 15m or
less.
(b) GOT side connector
For the GOT side connector, refer to the following.
1.4.1 GOT connector specifications
(c) ALLEN-BRADLEY PLC side connector
Use the connector compatible with the ALLEN-
BRADLEY PLC side module.
For details, refer to the ALLEN-BRADLEY PLC
user's manual.
RS232 connection diagram 1)
RS232 connection diagram 2)
RS232 connection diagram 3)
GOT side
ALLEN-BRADLEY PLC side
CD
RD(RXD)
SD(TXD)
ER(DTR)
SG
DR(DSR)
RS(RTS)
CS(CTS)
-
1
2
3
4
5
6
7
8
9
1
3
2
6
5
4
7
8
-
CD
TXD
RXD
DSR
SG
DTR
RTS
CTS
FG
GOT side
ALLEN-BRADLEY PLC side
CD
RD(RXD)
SD(TXD)
ER(DTR)
SG
DR(DSR)
RS(RTS)
CS(CTS)
-
1
2
3
4
5
6
7
8
9
1
2
3
6
7
20
4
5
8
FG
TXD
RXD
DSR
SG
DTR
RTS
CTS
CD
GOT side
ALLEN-BRADLEY PLC side
CD
RD(RXD)
SD(TXD)
ER(DTR)
SG
DR(DSR)
RS(RTS)
CS(CTS)
-
1
2
3
4
5
6
7
8
9
1
7
4
5
2
8
6
3
-
24V
TXD
RXD
CD
SG
SG
CTS
RTS
FG
RS232 connection diagram 4)
GOT side
ALLEN-BRADLEY PLC side
CD
RD(RXD)
SD(TXD)
ER(DTR)
SG
DR(DSR)
RS(RTS)
CS(CTS)
-
1
2
3
4
5
6
7
8
9
1
3
2
4
5
6
7
8
-
CD
TXD
RXD
DTR
SG
DSR
RTS
CTS
FG
Summary of Contents for GOT2000Series
Page 2: ......
Page 17: ...A 15 REVISIONS WARRANTY...
Page 52: ...1 30 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring...
Page 54: ......
Page 78: ...3 10 3 CONNECTION TO HITACHI PLC 3 6 Device Range that Can Be Set...
Page 100: ...4 22 4 CONNECTION TO FUJI PLC 4 7 Precautions...
Page 174: ...7 24 7 CONNECTION TO YOKOGAWA PLC 7 4 Device Range that Can Be Set...
Page 262: ...9 54 9 CONNECTION TO RKC TEMPERATURE CONTROLLER 9 7 Precautions...
Page 280: ...10 18 10 CONNECTION TO ALLEN BRADLEY PLC 10 4 Device Range that Can Be Set...
Page 296: ...11 16 11 CONNECTION TO GE PLC 11 7 Precautions...
Page 308: ...12 12 12 CONNECTION TO LS INDUSTRIAL SYSTEMS PLC 12 6 Device Range that Can Be Set...
Page 332: ...14 18 14 CONNECTION TO SIEMENS PLC 14 4 Device Range that Can Be Set...
Page 334: ...REVISIONS 2...
Page 337: ......