7. CONNECTION TO YOKOGAWA PLC
7.2 Serial Connection
7 - 13
7
CONN
ECTION
T
O
YOKOGA
W
A
PLC
(2) Data format setting switch
Set the data length, parity, stop bit and checksum
consistent with the corresponding settings on the GOT
side.
For the settings on the GOT side, refer to the following.
■
(3) Station No. switch (LC02-0N only)
7.2.11
Connecting to STARDOM
Make the communication settings as shown below.For
details of the communication settings, refer to the following
manual.
Peripheral Software Manual for YOKOGAWA
PLC
POINT
POINT
POINT
Connection between STARDOM and the PC for
communication settings
For the communication settings of STARDOM,
STARDOM and the PC for communication settings
must be connected to Ethernet using the Resource
Configurator (peripheral software).
COM port setting
Make the settings on the FCX Maintenance Page for
STARDOM.
1.
Select [Reboot (Maintenance Mode)] on the Reboot
screen of the FCX Maintenance Page to set the
maintenance mode.
2.
Set the COM1 port driver to be used.Execute [JEROS
Basic Setting File] from the [Edit System Setting File]
screen on the FCX Maintenance Page.
Confirm that the line of [Com1SioDriver] is as follows.
Com1SioDriver=DUONUS_SIO
3.
Set the COM1 port to be used.Execute [COM1 Port
Setting File] from the [Edit System Setting Files]
screen on the FCX Maintenance Page.Make the
settings as follows according to the communication
specifications on the setting screen.
Leave the settings as default if not listed on the
communication setting items.
(Communication setting items) ( ) in the table shows
the names on the FCX Maintenance Page.
*1
Adjust the settings with GOT communication settings.
■
Switch No.
Description
Settings
1
Data bit
ON (8bits),
OFF (7bits)
2
Parity
ON (done),
OFF (none)
3
ON (even),
OFF (odd)
4
Stop bit
ON (2bits),
OFF (1bit)
5
Checksum
ON (done),
OFF (none)
6
End character
specification
OFF (none)
7
Protect function
OFF (disabled)
8
—
OFF
Rotary
switch
Description
Settings
For RS-
232
communi
cation
For RS-
422
communi
cation
1)
Station No.
(10's digit)
0
0
2)
Station No.
(1's digit)
1
2
1
2
3
4
5
6
7
8
OFF
ON
0
6
5
4
7
3
8
2
9
1
0
6
5
4
7
3
8
2
9
1
STATION NO.
Item
Set value
Transmission speed (Baudrate)
*1
4800bps, 9600bps,
19200bps, 38400bps,
57600bps, 115200bps
Data length (DataBitLength)
*1
8bits, 7bits
Stop bit (StopBitLength)
*1
1bit, 2bits
Parity bit (Parity)
*1
none/odd/even
Baudrate
= *1
DataBitLength
= *1
StopBitLength
= *1
Parity
= *1
FifoMode
= YES
InitialDTRState
= ON
SendFlowControlMode
= CTS
ReceiveFlowControlMode
= DTR
Summary of Contents for GOT2000Series
Page 2: ......
Page 17: ...A 15 REVISIONS WARRANTY...
Page 52: ...1 30 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring...
Page 54: ......
Page 78: ...3 10 3 CONNECTION TO HITACHI PLC 3 6 Device Range that Can Be Set...
Page 100: ...4 22 4 CONNECTION TO FUJI PLC 4 7 Precautions...
Page 174: ...7 24 7 CONNECTION TO YOKOGAWA PLC 7 4 Device Range that Can Be Set...
Page 262: ...9 54 9 CONNECTION TO RKC TEMPERATURE CONTROLLER 9 7 Precautions...
Page 280: ...10 18 10 CONNECTION TO ALLEN BRADLEY PLC 10 4 Device Range that Can Be Set...
Page 296: ...11 16 11 CONNECTION TO GE PLC 11 7 Precautions...
Page 308: ...12 12 12 CONNECTION TO LS INDUSTRIAL SYSTEMS PLC 12 6 Device Range that Can Be Set...
Page 332: ...14 18 14 CONNECTION TO SIEMENS PLC 14 4 Device Range that Can Be Set...
Page 334: ...REVISIONS 2...
Page 337: ......