4. HOW TO MONITOR REDUNTANT SYSTEM
4.9 Q Redundant Setting
4 - 29
4
HOW T
O
MONIT
O
R R
EDUNT
ANT SYSTEM
4.9
Q Redundant Setting
The following explains the setting for automatically change the monitoring target of the GOT when monitoring a QCPU
redundant system.
POINT
POINT
POINT
Before making the Q redundant setting
In the Q redundant setting, do not set stations other than redundant CPUs.
1.
Select [Common]
[Controller Setting]
[Q Redundant] from the menu.
2.
The setting dialog box appears. Make the settings with reference to the following explanation.
3.
Make the settings for the Q redundant setting.
In the Q Redundant Setting dialog box, settings can be made for each channel of the controller.
(Example: Ethernet connection (Station No. 5), redundant CPU pair No. 1 and No. 2, redundant CPU station No. 1 to 4)
For details of *1, refer to the explanation below.
Item
Contents
Model
CH1 to CH4
Select a tab of the CH No. for the Q redundant setting.
Target at its own Station
(0-FF)
Select this item to monitor the control system as a host station.
(In Ethernet connection, not available even when selected)
Pair No.
*1
NW No.
Set the network No. (1 to 225) for each of pair numbers (1 to 64).
Upper row: Setting for the first redundant CPU.
Lower row: Setting for the second redundant CPU.
(The same value as the value set for the first redundant CPU is displayed)
Station
No.
Set the station No. (1 to 63) of the redundant CPU for each of pair numbers (1 to 64).
Upper row: Setting for the first redundant CPU.
Lower row: Setting for the second redundant CPU.
(The value of "Setting for the first redundant CPU" + 1 is displayed)
New
Create a new pair No.
Duplicate
Copies one setting of the selected pair number to append it at the last line.
Delete
Deletes one setting of the selected pair.
After deletion, the succeeding pair numbers are renumbered to fill the deleted pair number.
Delete All
Deletes the setting of all pair numbers.
Copy All
Copies the Q redundant setting on the selected CH No. tab.
Paste All
Pastes the copied Q redundant setting in the selected CH No. tab.
Summary of Contents for GOT2000 Series
Page 2: ......
Page 62: ...1 38 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring ...
Page 64: ......
Page 80: ...2 16 2 DEVICE RANGE THAT CAN BE SET 2 6 MELSEC WS ...
Page 246: ...7 26 7 COMPUTER LINK CONNECTION 7 6 Precautions ...
Page 252: ...8 6 8 BUS CONNECTION 8 1 Connectable Model List ...
Page 256: ...8 10 8 BUS CONNECTION 8 2 System Configuration ...
Page 288: ...8 42 8 BUS CONNECTION 8 4 Precautions ...
Page 324: ...9 36 9 MELSECNET H CONNECTION PLC TO PLC NETWORK MELSECNET 10 CONNECTION PLC TO PLC NETWORK ...
Page 416: ......
Page 510: ...15 46 15 SERVO AMPLIFIER CONNECTION 15 7 Precautions ...
Page 518: ...16 8 16 ROBOT CONTROLLER CONNECTION 16 6 Precautions ...
Page 540: ...17 22 17 CNC CONNECTION 17 7 Precautions ...
Page 541: ...MULTIPLE GOT CONNECTIONS 18 GOT MULTI DROP CONNECTION 18 1 ...
Page 542: ......
Page 567: ...MULTI CHANNEL FUNCTION 19 MULTI CHANNEL FUNCTION 19 1 ...
Page 568: ......
Page 599: ...FA TRANSPARENT FUNCTION 20 FA TRANSPARENT FUNCTION 20 1 ...
Page 600: ......
Page 668: ...20 68 20 FA TRANSPARENT FUNCTION 20 7 Precautions ...
Page 670: ...REVISIONS 2 ...
Page 673: ......