8 Program Example
8.1 System configuration
54
FX
3U
-64CCL User's Manual
•Example 2 for the master station settings
-
When the setting of the 64CCL is the single setting, please set up the master station as a Ver.1
intelligent device station. When the setting of the 64CCL are the double setting, the quadruple
setting, or the octuple setting, please set up the master station as a Ver.2 intelligent device station.
b) Set the station number, number of occupied stations/expanded cyclic transmission and transmission
rate/hardware test for the 64CCL.
Item
64CCL settings "A" for station number 1
64CCL settings "B" for station number 5
Station number
No. 1 (rotary switch)
No. 5 (rotary switch)
Number of occupied stations
/ expanded cyclic setting
4 stations / double
2 stations / single
Transmission rate /
hardware test setting
Align the transmission rate setting to match the setting in the master station.(rotary switch)
Number of remote points and
number assignment
The number of points and
assigned numbers are
determined by the number of
occupied stations/expanded
cyclic transmission setting.
Number of remote points and numbers for "4 stations/
double"
Remote input: RX00 to CF (208 points) User area
Remote input: RXD0 to DF (16 points) System area
Remote output: RY00 to CF (208 points) User area
Remote output: RYD0 to DF (16 points) System area
Remote register: RWr 00 to 1F (32 points) for write
Remote register: RWw 00 to 1F (32 points) for read
Number of remote points and numbers for "2 stations/
single"
Remote input: RX00 to 2F (48 points) User area
Remote input: RX30 to 3F (16 points) System area
Remote output: RY00 to 2F (208 points) User area
Remote output: RY30 to 3F (16 points) System area
Remote register: RWr 00 to 07 (8 points) for write
Remote register: RWw 00 to 07 (8 points) for read