This manual confers no industrial property rights or any rights of any other kind,
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
Warranty
Exclusion of loss in opportunity and secondary loss from warranty liability
Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to:
(1) Damages caused by any cause found not to be the responsibility of Mitsubishi.
(2) Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products.
(3) Special damages and secondary damages whether foreseeable or not, compensation for
accidents, and compensation for damages to products other than Mitsubishi products.
(4) Replacement by the user, maintenance of on-site equipment, start-up test run
and other tasks.
For safe use
This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in
a device or system used in purposes related to human life.
Before using the product for special purposes such as nuclear power, electric
power, aerospace, medicine or passenger movement vehicles, consult with
Mitsubishi Electric.
This product has been manufactured under strict quality control. However
when installing the product where major accidents or losses could occur if the
product fails, install appropriate backup or failsafe functions in the system.
•
•
•
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Side
A
Side
B
JAPANESE
ENGLISH
JY997D38901C
Side
B
Note: This symbol mark is for China only.
含有有害6物质的名称,含有量,含有部品
本产品中所含有的有害6 物质的名称,含有量,含有部品如下表
所示。
产品中有害物质的名称及含量
本表格依据SJ/T 11364的规定编制。
○:表示该有害物质在该部件所有均质材料中的含量均在GB/T 26572
规定的限量要求以下。
×:表示该有害物质至少在该部件的某一均质材料中的含量超出GB/T
26572规定的限量要求。
部件名称
有害物质
铅
(Pb)
汞
(Hg)
镉
(Cd)
六价铬
(Cr(VI))
多溴联苯
(PBB)
多溴
二苯醚
(PBDE)
可编程
控制器
外壳
印刷基板
○
○
○
○
○
○
○
○
○
○
○
×
「电器电子产品有害物质限制使用标识要求」的表示方式
基于中国标准法的参考规格:GB/T15969.2
Safety Precautions
(Read these precautions before use.)
This manual classifies the safety precautions into two categories:
and
.
Depending on the circumstances, procedures indicated by
may also
cause severe injury.
It is important to follow all precautions for personal safety.
Associated Manuals
How to obtain manuals
For product manuals or documents, consult with the Mitsubishi Electric dealer
from who you purchased your product.
Certification of UL, cUL standards
FX
3U
-4LC units comply with the UL standards (UL, cUL).
UL, cUL File Number: E95239
Regarding the standards that comply with the main unit, please refer to either the
FX series product catalog or consult with your nearest Mitsubishi product provider.
Indicates that incorrect handling may cause hazardous
conditions, resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous
conditions, resulting in medium or slight personal injury or
physical damage.
Manual name
Manual No.
Description
FX
3U
-4LC
User's Manual
JY997D39101
MODEL CODE:
09R625
Describes details of the FX
3U
-
4LC temperature control block.
FX
3G
Series
User’s Manual
- Hardware Edition
JY997D31301
MODEL CODE:
09R521
Explains the FX
3G
Series PLC
specifications for I/O, wiring,
installation, and maintenance.
FX
3GC
Series
User's Manual
- Hardware Edition
JY997D45401
MODEL CODE:
09R533
Explains the FX3GC Series PLC
specifications for I/O, wiring,
installation, and maintenance.
FX
3U
Series
User’s Manual
- Hardware Edition
JY997D16501
MODEL CODE:
09R516
Explains the FX
3U
Series PLC
specifications for I/O, wiring,
installation, and maintenance.
FX
3UC
Series
User’s Manual
- Hardware Edition
JY997D28701
MODEL CODE:
09R519
Explains the FX
3UC
Series PLC
specifications for I/O, wiring,
installation, and maintenance.
MELSEC iQ-F
FX5U User's
Manual (Hardware)
JY997D55301
MODEL CODE:
09R536
Explains the FX5U PLC
specifications for I/O, wiring,
installation, and maintenance.
MELSEC iQ-F
FX5UC User's
Manual (Hardware)
JY997D61401
MODEL CODE:
09R558
Explains the FX5UC PLC
specifications for I/O, wiring,
installation, and maintenance.
Compliance with EC directive (CE Marking)
This note does not guarantee that an entire mechanical module produced in
accordance with the contents of this note will comply with the following standards.
Compliance to EMC directive and LVD directive for the entire mechanical module
should be checked by the user / manufacturer. For more information please consult
with your nearest Mitsubishi product provider.
Regarding the standards that comply with the main unit, please refer to either the FX
series product catalog or consult with your nearest Mitsubishi product provider.
Requirement for Compliance with EMC directive
The following products have shown compliance through direct testing (of the identified
standards below) and design analysis (through the creation of a technical construction
file) to the European Directive for Electromagnetic Compatibility (2014/30/EU) when
used as directed by the appropriate documentation.
Attention
This product is designed for use in industrial applications.
Type:
Programmable Controller (Open Type Equipment)
Models:
MELSEC FX
3U
series manufactured
from December 1st, 2009 FX
3U
-4LC
Caution for EC Directive
The FX
3U
-4LC have been found to be compliant to the European standards in the
aforesaid manual and directive. However, for the very best performance from what are
in fact delicate measuring and controlled output device Mitsubishi Electric would like to
make the following points;
As analog devices are sensitive by nature, their use should be considered carefully.
For users of proprietary cables (integral with sensors or actuators), these users should
follow those manufacturers installation requirements.
Mitsubishi Electric recommend that shielded cables should be used. If NO other EMC
protection is provided, then users may experience temporary loss or accuracy between
±10% in very heavy industrial areas.
However, Mitsubishi Electric suggest that if adequate EMC precautions are followed for
the users complete control system, users should expect accuracy as specified in this
manual.
•
Sensitive analog cable should not be laid in the same trunking or cable conduit as
high voltage cabling. Where possible users should run analog cables separately.
•
Good cable shielding should be used. When terminating the shield at Earth
- ensure that no earth loops are accidentally created.
•
When reading analog values, EMC accuracy can be improved out by averaging the
readings. This can be achieved either through functions on the analog special
function blocks or through a users program in the FX
3G
/FX
3U
/FX
3UC
Series PLC
main unit.
•
Installation in Enclosure
Programmable logic controllers are open-type devices that must be installed and
used within conductive control cabinets. Please use the programmable logic
controller while installed within a conductive shielded control cabinet. Please secure
the cabinet door to the control cabinet (for conduction). Installation within a control
cabinet greatly affects the safety of the system and aids in shielding noise from the
programmable logic controller.
1. Introduction
The temperature control block FX
3U
-4LC (hereinafter called 4LC) equipped with 4
channel input (thermocouples, resistance thermometer and micro voltage input), 4
points output (open collector transistor) and 4 points CT input is a special function
block for thermometer control.
→
For details, refer to the FX
3U
-4LC User's Manual.
1.1 Incorporated Items
Check to ensure the following product and items are included in the package
Standard
Remark
EN61131-2:2007
Programmable controllers
- Equipment requirements
and tests
Compliance with all relevant aspects of the
standard.
EMI
• Radiated Emission
• Conducted Emission
EMS
• Radiated electromagnetic field
• Fast transient burst
• Electrostatic discharge
• High-energy surge
• Voltage drops and interruptions
• Conducted RF
• Power frequency magnetic field
Included Item
FX
3U
-4LC
1 unit
Special unit/block No. label
1 sheet
Dust proof protection sheet
1 sheet
Manuals (Japanese version, English version)
1 manual each
1.2 External Dimensions and Part Names
1.3 Power and status LEDs
1.4 Terminal Layout
2. Installation
For installation details, refer to the following manuals.
→
Refer to the FX
3U
-4LC User's Manual.
[1]
Extension cable
[6]
Status LEDs (Red)
[2]
Direct mounting hole
2 holes of
4.5 (0.18")
(mounting screw: M4 screw)
[7]
Extension connector
[3]
Terminal block covers
[8]
Nameplate
[4]
Terminal cover
[9]
DIN rail mounting groove
( D I N r a i l : D I N 4 6 2 7 7 , 3 5 m m
(1.38") width)
[5]
Power LED (green)
[10]
DIN rail mounting hook
LED
display
LED
color
Status
Description
POWER
Green
OFF
Power is not being supplied from the internal power
supply (5V DC).
ON
Power is being supplied from the internal power supply
(5V DC).
24V
Red
OFF
Power is not being supplied from the external power
supply (24V DC).
ON
Power is being supplied from the external power
supply (24V DC).
OUT1 to
OUT4
Red
OFF
OUT1 to OUT4 output OFF
ON
OUT1 to OUT4 output ON
INSTALLATION
PRECAUTIONS
•
Make sure to shut down all phases of the power supply externally before
installing. Failure to do so may cause electric shock or damage to the product.
INSTALLATION
PRECAUTIONS
•
Use the product within the generic environment specifications described in PLC
main unit manual (Hardware Edition).
Never use the product in areas with excessive dust, oily smoke, conductive dusts,
corrosive gas (salt air, Cl
2
, H
2
S, SO
2
or NO
2
), flammable gas, vibration or impacts,
or expose it to high temperature, condensation, or rain and wind.
If the product is used in such conditions, electric shock, fire, malfunctions,
deterioration or damage may occur.
2-Ø4.5 mounting holes
[1] [2]
[4] [5]
[6]
82(3.23")
(mounting hole pitch)
90(3.55")
[4]
[8]
[9]
[10]
86(3.39")
9(0.36")
Unit: mm(inches)
MASS(Weight) : Approx. 0.4kg(0.88lbs)
Terminal screws: M3
82(3.23")
(mounting hole pitch)
90(3.55")
[7]
[3]
[3]
24+
24-
CT
FG
CT
CT
FG
CT
OUT1 OUT2
COM1
OUT3 OUT4
CT
FG
CT
FG
CT
CT
COM2
CH1
CH4
CH2
CH3
PTA/ /
PTB/TC-/COM
PTB/TC-/COM
PTB/TC+/VL+
PTA/ / PTB/TC+/VL+
PTB/TC-/COM
PTB/TC-/COM
PTB/TC+/VL+
PTB/TC+/VL+
PTA/ /
PTA/ /
2.1 Connection with PLC
The 4LC connects on the right side of an PLC main unit or extension units/blocks
(including special function units/blocks).
For connection to an FX
3GC
/FX
3UC
Series PLC or FX
2NC
Series PLC extension
block, an FX
2NC
-CNV-IF or FX
3UC
-1PS-5V is required.
For details, refer to the respective PLC manual.
→
Refer to the FX
3G
Series User's Manual - Hardware Edition.
→
Refer to the FX
3GC
Series User's Manual - Hardware Edition.
→
Refer to the FX
3U
Series User's Manual - Hardware Edition.
→
Refer to the FX
3UC
Series User's Manual - Hardware Edition.
→
Refer to the MELSEC iQ-F FX5U User's Manual (Hardware).
→
Refer to the MELSEC iQ-F FX5UC User's Manual (Hardware).
2.2 Mounting
The product is mounted by the following method.
•
DIN rail mounting
•
Direct mounting (mounting screw: M4 screw)
For details, refer to the respective PLC manual.
→
Refer to the FX
3G
Series User's Manual - Hardware Edition.
→
Refer to the FX
3GC
Series User's Manual - Hardware Edition.
→
Refer to the FX
3U
Series User's Manual - Hardware Edition.
→
Refer to the FX
3UC
Series User's Manual - Hardware Edition.
→
Refer to the MELSEC iQ-F FX5U User's Manual (Hardware).
→
Refer to the MELSEC iQ-F FX5UC User's Manual (Hardware).
3. Wiring
For wiring details, refer to the following manuals.
→
Refer to the FX
3U
-4LC User's Manual.
INSTALLATION
PRECAUTIONS
•
Do not touch the conductive parts of the product directly.
Doing so may cause device failures or malfunctions.
•
Install the product securely using a DIN rail or mounting screws.
•
Install the product on a flat surface.
If the mounting surface is rough, undue force will be applied to the PC board,
thereby causing nonconformities.
•
When drilling screw holes or wiring, make sure that cutting and wiring debris
do not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
•
Be sure to remove the dust proof sheet from the PLC's ventilation slits when
installation work is completed.
Failure to do so may cause fire, equipment failures or malfunctions.
•
Connect extension cables securely to their designated connectors.
Loose connections may cause malfunctions.
WIRING
PRECAUTIONS
•
Make sure to cut off all phases of the power supply externally before
attempting wiring work.
Failure to do so may cause electric shock.
WIRING
PRECAUTIONS
•
Connect the AC power supply to the dedicated terminals specified in this
manual. If an AC power supply is connected to a DC input/output terminal or
DC power supply terminal, the PLC will burn out.
•
Do not wire vacant terminals externally. Doing so may damage the product.
•
Use class D grounding (grounding resistance of 100
Ω
or less) with a wire of
2mm
2
or thicker on the grounding terminal of the PLC. However, do not
connect the ground terminal at the same point as a heavy electrical system.
•
When drilling screw holes or wiring, make sure cutting or wire debris does
not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
•
Make sure to observe the following precautions in order to prevent
malfunctions under the influence of noise.
- Do not bundle the power line or twisted shielded cable together with or lay
it close to the main circuit, high-voltage line, or load line.
Otherwise, noise disturbance and/or surge induction are likely to take
place. As a guideline, lay the control line at least 100mm (3.94") or more
away from the main circuit, high-voltage line, or load line.
- Ground the shield wire or shield of the shielded cable at one point on the
PLC. However, do not use common grounding with heavy electrical
systems.
•
Make sure to properly wire to the terminal blocks in accordance with the
following precautions. Failure to do so may cause electric shock, a short-
circuit, wire breakage, or damage to the product.
- The disposal size of the cable end should follow the dimensions
described in the FX
3U
-4LC User's Manual
- Tightening torque should follow the specifications in the FX
3U
-4LC User's
Manual
3.1 Example of Input/output Wiring
*1 24V DC service power supply of the FX
3G
/FX
3U
Series PLC can also be used.
*2 When using a thermocouple, use specified compensating lead wires.
*3 When you use a resistance thermometer sensor, the resistance of the lead
wire is low, use a wire without a resistance difference between the lead wire.
*4 Make sure to short-circuit the 'PTB' and 'PTB' terminals when a 2-wire
resistance thermometer sensor is input.
3.2 Grounding
Ground the cables as follows
•
The grounding resistance should be 100
Ω
or less.
•
Independent grounding should be established whenever possible.
Independent grounding should be performed for best results.
When independent grounding is not configured, perform "shared grounding" as
shown in the following figure. For details, refer to the respective PLC manual.
→
Refer to the FX
3G
Series User's Manual - Hardware Edition.
→
Refer to the FX
3GC
Series User's Manual - Hardware Edition.
→
Refer to the FX
3U
Series User's Manual - Hardware Edition.
→
Refer to the FX
3UC
Series User's Manual - Hardware Edition.
→
Refer to the MELSEC iQ-F FX5U User's Manual (Hardware).
→
Refer to the MELSEC iQ-F FX5UC User's Manual (Hardware).
•
The grounding point should be close to the 4LC, and all grounding wires
should be as short as possible.
4. Specification
For details on specifications, refer to the following manual.
→
Refer to the FX
3U
-4LC User's Manual.
DESIGN
PRECAUTIONS
•
Make sure to include the following safety circuits outside the PLC to ensure
safe system operation even during external power supply problems or PLC
failure. Otherwise, malfunctions may cause serious accidents.
1) Above all, the following components should be included: an emergency
stop circuit, a protection circuit, an interlock circuit for opposite movements
(such as normal vs. reverse rotation), and an interlock circuit (to prevent
damage to the equipment at the upper and lower positioning limits).
2) Note that when the PLC CPU detects an error, such as a watchdog timer
error, during self-diagnosis, all outputs are turned off. Also, when an error
that cannot be detected by the PLC CPU occurs in an input/output
control block, output control may be disabled.
External circuits and mechanisms should be designed to ensure safe
machinery operation in such a case.
3) Note that when an error occurs in a relay, triac or transistor output
device, the output could be held either on or off. For output signals that
may lead to serious accidents, external circuits and mechanisms should
be designed to ensure safe machinery operation in such a case.
DESIGN
PRECAUTIONS
•
Do not bundle the control line together with or lay it close to the main circuit
or power line. As a guideline, lay the control line at least 100mm (3.94") or
more away from the main circuit or power line. Noise may cause
malfunctions.
COM
VL+
FG
24+
24-
TC-
FG
TC+
Shielded wire
Shielded wire
Shielded wire
PTB
PTB
PTA
FG
PTB
PTB
PTA
FG
Shielded wire
OUT1
COM1
Load
Output
Voltage input
Thermocouple
Power supply
*4
ch
ch
ch
ch
: represents the channel number.
ch
FX
3U
-4LC
24V DC
*1
Compensating lead wire
*2
Pt1000
(2-wire type
*3
)
Pt100 or Pt1000
(3-wire type
*3
)
Grounding
(Ground
resistance:
100
Ω
or less)
4LC
4LC
4LC
Other
equipment
Other
equipment
Other
equipment
Shared grounding
Good condition
Common grounding
Not allowed
Independent grounding
Best condition
4.1 Applicable PLC
The version number can be checked by reading the last three digits of device D8001/
D8101.
*1 An FX
2NC
-CNV-IF or FX
3UC
-1PS-5V is necessary to connect the 4LC with the
FX
3GC
/FX
3UC
PLC.
*2 An FX5-CNV-BUS or FX5-CNV-BUSC is necessary to connect the 4LC with the
FX5U/FX5UC PLC.
*3 Up to 7 units can be connected to the FX
3UC
-32MT-LT(-2) PLC.
4.2 General Specifications
Items other than the following are equivalent to those of the PLC main unit.
For general specifications, refer to the manual of the PLC main unit.
→
Refer to the FX
3G
Series User's Manual - Hardware Edition.
→
Refer to the FX
3GC
Series User's Manual - Hardware Edition.
→
Refer to the FX
3U
Series User's Manual - Hardware Edition.
→
Refer to the FX
3UC
Series User's Manual - Hardware Edition.
→
Refer to the MELSEC iQ-F FX5U User's Manual (Hardware).
→
Refer to the MELSEC iQ-F FX5UC User's Manual (Hardware).
4.3 Power Supply Specification
4.4 Performance Specification
DESIGN
PRECAUTIONS
•
Ground the shield wire or shield of the shielded cable at one point on the PLC.
However, do not ground them at the same point as the high-voltage lines.
Noise may cause malfunctions.
•
Install module so that excessive force will not be applied to the terminal blocks.
Failure to do so may result in wire damage/breakage or PLC failure.
DISPOSAL
PRECAUTIONS
•
Please contact a certified electronic waste disposal company for the
environmentally safe recycling and disposal of your device.
TRANSPORT AND
STORAGE PRECAUTIONS
•
The product is a precision instrument. During transportation, avoid impacts larger
than those specified in the general specifications by using dedicated packaging
boxes and shock-absorbing palettes. Failure to do so may cause failures in the
product. After transportation, verify operation of the product and check for
damage of the mounting part, etc.
Model name
Applicability
FX
3G
Series PLC
Ver. 1.00 and later (Up to 8 blocks can be extended)
FX
3GC
Series PLC
*1
Ver. 1.40 and later (Up to 6 blocks can be extended)
FX
3U
Series PLC
Ver. 2.20 and later (Up to 8 blocks can be extended)
FX
3UC
Series PLC
*1
Ver. 2.20 and later (Up to 8 blocks can be extended
*3
)
FX5U PLC
*2
From first production (Up to 8 blocks can be extended)
FX5UC PLC
*2
From first production (Up to 6 blocks can be extended)
Item
Specification
Dielectric withstand
voltage
500V AC for one minute
Between all terminals and
ground terminal
Insulation resistance
5M
Ω
or higher by 500V DC
insulation resistance tester
Item
Specification
Interface driving power
supply
24V DC +20% -15% 50mA
Connect a 24V DC power supply to the terminal block.
CPU driving power
5V DC 160mA
5V DC power is supplied internally from the main unit.
Item
Specification
Control method
Two-position control, PID control,
Heating/cooling PID control, Cascade control
Control operation period
250ms/4ch
Set temperature range
Refer to section 4.7
Heater disconnection
detection
Alarm is detected by buffer memory
(Variable within range from 0.0 to 100.0A.)
Operation mode
0 : Not used, 1 : Monitor, 2 : Alarm,
3 : Alarm+Control (Selected by buffer memory)
Self-diagnosis function
Adjustment data check, input value check, watch dog
timer check.
Memory
Built-in EEPROM
(Number of times of overwrite : 100.000 times)
Insulation method
•
The photocoupler is used to insulate the analog input
area and transistor output area from the PLC.
•
The DC/DC converter is used to insulate the power
supply from the analog input area and transistor
output area.
•
Channels are insulated from each other.
4.5 Input Specification
*1 A different input can be selected for each channel.
*2 Measurement accuracy differs depending on the type of input, and the input
range. For specification details, refer to the following manuals.
→
Refer to the FX
3U
-4LC User's Manual.
4.6 Current sensor (CT) Input Specifications
4.7 Set temperature range
Number of I/O occupied
points
8 points
(Taken from either the input or output points of the PLC.)
Item
Specification
Number of input points
4 points
Input type
*1
Thermocouple
K, J, R, S, E, T, B, N JIS C 1602-1995,
PLII, W5Re/W26Re, U, L
R e s i s t a n c e
thermometer
3-wire type Pt100 JIS C 1604-1997,
3-wire type JPt100 JIS C 1604-1981
2-wire type/3-wire type
Pt1000 JIS C 1604-1997
Micro voltage input
Measurement precision
When ambient
temperature is
25
°
C
±
5
°
C
K type thermocouple : When the input is
in the range of 500
°
C or more
±
(0.3% of input value)
±
1digit
*2
When ambient
temperature is
0 to 55
°
C
K type thermocouple : When the input is
in the range of 500
°
C or more
±
(0.7% of input value)
±
1digit
*2
Cold contact temperature
compensation error
Within
±
1.0
°
C (When ambient temperature is 0 to 55
°
C)
However, within
±
2.0
°
C while input value is
-150 to -100
°
C / within
±
3.0
°
C while input value is -200
to -150
°
C
Resolution
0.1
°
C (0.1
°
F), 1
°
C (1
°
F), 0.5
µ
V or 5.0
µ
V
Varies depending on input range of used sensors.
Sampling period
250ms/4ch
Effect of external
resistance (When
thermocouple is used)
Approx. 0.125
µ
V/
Ω
Effect of input lead wire
resistance
(When resistance
thermometer is used)
3-wire type
Approx. 0.03%/
Ω
of full scale.
10
Ω
or less per 1-wire
2-wire type
Approx. 0.04%/
Ω
of full scale.
7.5
Ω
or less per 1-wire
Input impedance
1M
Ω
or more
Sensor current
Approx. 0.25mA
(When resistance thermometer is used)
Operation when input is
disconnected/
Operation when input is
short-circuited
Upscale/
Downscale (When resistance thermometer is used)
Item
Specification
Number of input points
4 points
Current sensor
CTL-12-S36-8, CTL-12-S56-10, CTL-6-P-H
(manufactured by U.R.D. Co., Ltd.)
Heater current measured value
When CTL-12-S36-8 is used : 0.0 to 100.0A
When CTL-12-S56-10 is used : 0.0 to 100.0A
When CTL-6-P-H is used : 0.0 to 30.0A
Measurement precision
Larger one between
±
5% of input value and
±
2A
(Excluding precision of current sensor)
Sampling period
0.5 sec.
Item
Specification
K
-200 to 1300
°
C (-100 to 2400
°
F)
J
-200 to 1200
°
C (-100 to 2100
°
F)
T
-200 to 400
°
C (-300 to 700
°
F)
S
0 to 1700
°
C (0 to 3200
°
F)
R
0 to 1700
°
C (0 to 3200
°
F)
E
-200 to 1000
°
C (0 to 1800
°
F)
B
0 to 1800
°
C (0 to 3000
°
F)
N
0 to 1300
°
C (0 to 2300
°
F)
PLII
0 to 1200
°
C (0 to 2300
°
F)
W5Re/W26Re
0 to 2300
°
C (0 to 3000
°
F)
U
-200 to 600
°
C (-300 to 700
°
F)
Item
Specification
4.8 Output Specification
Item
Specification
L
0 to 900
°
C (0 to 1600
°
F)
Micro voltage input
DC0 to 10mV, DC0 to 100mV
Pt100 (3-wire type)
-200 to 600
°
C (-300 to 1100
°
F)
JPt100 (3-wire type)
-200 to 500
°
C (-300 to 900
°
F)
Pt1000 (2-wire type/3-wire type)
-200.0 to 650.0
°
C (-328 to 1184
°
F)
Item
Specification
Number of output points
4 points
Output method
NPN open collector transistor output
Rated load voltage
5 to 24V DC
Maximum load voltage
30V DC or less
Maximum load current
100mA
Leak current in OFF status
0.1mA or less
ON voltage
1.5V (When the maximum load current)
Control output cycle
0.5 to 100.0 sec.
FX
3U
-4LC
INSTALLATION MANUAL
This manual describes the part names, dimensions, mounting, and specifications
of the product. Before use, read this manual and the manuals of all relevant
products fully to acquire proficiency in handling and operating the product. Make
sure to learn all the product information, safety information, and precautions.
Store this manual in a safe place so that it can be taken out and read whenever
necessary. Always forward it to the end user.
Registration: