This manual confers no industrial property rights or any rights of any other kind,
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
Warranty
Exclusion of loss in opportunity and secondary loss from warranty liability
Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to:
(1) Damages caused by any cause found not to be the responsibility of Mitsubishi.
(2) Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products.
(3) Special damages and secondary damages whether foreseeable or not, compensation for
accidents, and compensation for damages to products other than Mitsubishi products.
(4) Replacement by the user, maintenance of on-site equipment, start-up test run
and other tasks.
For safe use
This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in
a device or system used in purposes related to human life.
Before using the product for special purposes such as nuclear power, electric
power, aerospace, medicine or passenger movement vehicles, consult with
Mitsubishi Electric.
This product has been manufactured under strict quality control. However
when installing the product where major accidents or losses could occur if the
product fails, install appropriate backup or failsafe functions in the system.
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Safety Precautions
(Read these precautions before use.)
This manual classify the safety precautions into two categories:
and
.
Depending on the circumstances, procedures indicated by
may also
cause severe injury.
It is important to follow all precautions for personal safety.
Associated Manuals
How to obtain manuals
For the necessary product manuals or documents, consult with the Mitsubishi
Electric dealer from where you purchase your product.
Indicates that incorrect handling may cause hazardous
conditions, resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous
conditions, resulting in medium or slight personal injury
or physical damage.
Manual name
Manual No.
Description
FX
3S
Series User’s Manual
- Hardware Edition
JY997D48601
MODEL CODE:
09R535
Explains FX
3S
Series PLC
specification details for I/O,
w i r i n g , i n s t a l l a t i o n , a n d
maintenance.
FX
3G
Series User’s Manual
- Hardware Edition
JY997D31301
MODEL CODE:
09R521
Explains FX
3G
Series PLC
specification details for I/O,
w i r i n g , i n s t a l l a t i o n , a n d
maintenance.
FX
3S
/FX
3G
/FX
3GC
/FX
3U
/
FX
3UC
Series
Programming Manual
- Basic & Applied Instruction
Edition
JY997D16601
MODEL CODE:
09R517
Describes PLC programming
for basic/applied instructions
and devices.
Applicable standards
FX
3G
-4EX-BD
units made in September, 2013 or later comply with the EC Directive
(EMC Directive). Further information can be found in the following manual.
→
FX
3S
Series User's Manual - Hardware Edition
→
FX
3G
Series User's Manual - Hardware Edition
Regarding the standards that relate to the main unit, please refer to either the FX
series product catalog or consult with your nearest Mitsubishi product provider.
Attention
This product is designed for use in industrial applications.
1. Outline
The
FX
3G
-4EX-BD
input expansion board (hereinafter referred to as "
4EX-BD
") is an
expansion board to be installed in the
FX
3S
or
FX
3G
series programmable controller
(hereinafter referred to as "PLC"), to add four additional inputs.
1.1 Incorporated Items
Verify that the following product and items are included in the package:
1.2 External Dimensions and Part Names
[1] Terminal block mounting screws
[2] Input LED
BX0 LED: The LED is lit when BX0 is on.
BX1 LED: The LED is lit when BX1 is on.
BX2 LED: The LED is lit when BX2 is on.
BX3 LED: The LED is lit when BX3 is on.
[3] Mounting holes (2-
φ
3.2)
[4] Connector cover
[5] Main unit connector
[6] Terminal block for input (European)
[7] Memory cassette/Display module connector
Product
FX
3G
-4EX-BD
input expansion board
Accessories
•
M3
×
8 tapping screws for installation: 2 pcs.
•
Side cover
•
USER’S MANUAL (This manual)
S/S
BX0
BX1
BX2
BX3
14.1
15.1
Unit: mm (inches)
35 (1.38")
51.2 (2.02")
[4]
[3]
[5]
[7]
Connector cover is
removed
MASS (Weight):
Approx. 20 g (0.05 lbs)
[6]
[1]
(0.6") (0.56")
[2]
5 poles
Terminal Layout
BX1
LEDs correspond to each input terminal
BX3
BX2
BX0
2. Installation
For installation/uninstallation details, refer to the following manual.
→
FX
3S
Series User's Manual - Hardware Edition
→
FX
3G
Series User's Manual - Hardware Edition
3. Wiring
INSTALLATION
PRECAUTIONS
•
Make sure to cut off all phases of the power supply externally before attempting
installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
INSTALLATION
PRECAUTIONS
•
Use the product within the generic environment specifications described in PLC
main unit manual (Hardware Edition).
Never use the product in areas with excessive dust, oily smoke, conductive dusts,
corrosive gas (salt air, Cl
2
, H
2
S, SO
2
or NO
2
), flammable gas, vibration
or impacts, or expose it to high temperature, condensation, or rain and wind.
If the product is used in such conditions, electric shock, fire, malfunctions,
deterioration or damage may occur.
•
Make sure to affix the expansion board with tapping screws.
Tightening torque should follow the specifications in the manual.
Loose connections may cause malfunctions.
•
Use screwdrivers carefully when performing installation work, thus avoiding
accident or product damage.
•
When drilling screw holes or wiring, make sure that cutting and wiring debris do
not enter the ventilation slits of the PLC.
Failure to do so may cause fire, equipment failures or malfunctions.
•
Do not touch the conductive parts of the product directly.
Doing so may cause device failures or malfunctions.
•
Connect expansion board securely to their designated connectors.
Loose connections may cause malfunctions.
DESIGN
PRECAUTIONS
•
Make sure to have the following safety circuits outside of the PLC to ensure safe
system operation even during external power supply problems or PLC failure.
Otherwise, malfunctions may cause serious accidents.
1) Most importantly, have the following: an emergency stop circuit, a protection
circuit, an interlock circuit for opposite movements (such as normal vs.
reverse rotation), and an interlock circuit (to prevent damage to the equipment
at the upper and lower positioning limits).
2) Note that when the PLC CPU detects an error, such as a watchdog timer
error, during self-diagnosis, all outputs are turned off. Also, when an error that
cannot be detected by the PLC CPU occurs in an input/output control block,
output control may be disabled.
External circuits and mechanisms should be designed to ensure safe
machinery operation in such a case.
3) If an overload of the 24 V DC service power supply occurs, the voltage
automatically drops, inputs in the PLC are disabled, and all outputs are turned
off.
External circuits and mechanisms should be designed to ensure safe
machinery operation in such a case.
DESIGN
PRECAUTIONS
•
Do not bundle the control line together with or lay it close to the main circuit or
power line. As a guideline, lay the control line at least 100 mm (3.94") or more
away from the main circuit or power line.
Noise may cause malfunctions.
WIRING
PRECAUTIONS
•
Make sure to cut off all phases of the power supply externally before attempting
installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
WIRING
PRECAUTIONS
•
Connect the DC power supply to the dedicated terminals specified in the manual
of the PLC main unit.
If an AC power supply is connected to a DC input/output terminal or DC power
supply terminal, the PLC will burn out.
3.1 Applicable Cable and Terminal Tightening Torque
3.1.1
Terminal block (European type)
1) Wire size
Wiring to input device should use 22 to 20 AWG wire.
2) Applicable cable
3) Termination of cable end
Strip the coating of strand wire and twist the cable core before connecting it,
or strip the coating of single wire before connecting it.
An alternative connection is to use a ferrule with insulating sleeve.
<Reference>
*1 Old model name: CRIMPFOX ZA 3
*2 Old model name: CRIMPFOX UD 6
When using a ferrule with insulation sleeve, choose a wire with proper cable
sheath referring to the above outside dimensions, or otherwise, the wire
cannot be inserted easily.
The tightening torque must be 0.22 to 0.25 N
•
m. Do not tighten terminal
screws exceeding the specified torque. Failure to do so may cause equipment
failures or malfunctions.
4) Tool
For tightening the terminal, use a
commercially available small
screwdriver having a straight form that is
not widened toward the end as shown
right.
Caution:
If the diameter of screwdriver grip is too
small, tightening torque will not be able
to be achieved. Use the following recommended screwdriver or an
appropriate replacement (grip diameter: approximately 25 mm (0.98")).
<Reference>
WIRING
PRECAUTIONS
•
When drilling screw holes or wiring, make sure cutting or wire debris does not
enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
•
Make sure to observe the following precautions in order to prevent
malfunctions under the influence of noise:
- Do not bundle the power line or input line together with or lay it close to the
main circuit, high-voltage line or load line.
Otherwise, noise disturbance and/or surge induction are likely to take
place.
As a guideline, lay the control line at least 100mm (3.94") or more away
from the main circuit or high-voltage lines.
•
Make sure to properly wire to the terminal block (European type) in
accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit,
wire breakage, malfunctions, or damage to the product.
- The disposal size of the cable end should follow the dimensions described
in the manual.
- Tightening torque should follow the specifications in the manual.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires
of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected
parts are directly stressed.
Type
Wire size
Single-wire
0.3 to 0.5 mm
2
(AWG22 to 20)
2-wire
2 pieces of 0.3 mm
2
(AWG22)
Manufacturer
Model
Caulking tool
Phoenix Contact Co., Ltd.
AI 0.5-8WH
CRIMPFOX 6
*1
(or CRIMPFOX 6T-F
*2
)
Manufacturer
Model
Phoenix Contact Co., Ltd.
SZS 0.4
×
2.5
9mm
(0.35")
- Strand wire/single wire
8mm
(0.31")
Contact area
(Crimp area)
14mm(0.55")
2.6mm(0.1")
Insulation sleeve
- Ferrule with insulation sleeve
With
straight tip
2.5mm
(0.1")
0.4mm
(0.02")
3.2 Wiring of input
→
For the terminal configuration, refer to Section 1.2
Sink input wiring
Source input wiring
*1 The service power supply of the PLC main unit can be used.
3.3 Grounding
Grounding should be performed as stated below.
•
The grounding resistance should be 100
Ω
or less.
•
Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" of
the following figure.
For details, refer to the following manual.
→
FX
3S
Series User's Manual - Hardware Edition
→
FX
3G
Series User's Manual - Hardware Edition
•
The grounding wire size should be AWG 22 to 20 (0.3 to 0.5 mm
2
).
•
The grounding point should be close to the PLC, and all grounding wire should
be as short as possible.
3.4 Instructions for connecting input devices
The input current of this PLC is 5 mA/24 V DC. Use input devices applicable to
this minute current.
If no-voltage contacts (switches) for large current are used, contact failure may occur.
<Example> Products of OMRON
3.4.1
In the case of input device with built-in series diode
The voltage drop of the series diode should be approx. 4 V or less.
When lead switches with a series LED are used, up to two switches can be
connected in series. Also make sure that the input current is over the input-
sensing level while the switches are ON.
Sink input wiring Source input wiring
*1 BX
:
represents the input number of 4EX-BD.
Type
Model name
Type
Model name
Microswitch
Models Z, V
and D2RV
Operations switch
Model A3P
Proximity switch
Model TL
Photoelectric
switch
Model E3S
S/S
24 V DC
*1
4EX-BD
4.3 k
Ω
BX0
BX1
BX3
BX2
4.3 k
Ω
4.3 k
Ω
4.3 k
Ω
S/S
4EX-BD
4.3 k
Ω
BX0
BX1
BX3
BX2
4.3 k
Ω
4.3 k
Ω
4.3 k
Ω
24 V DC
*1
PLC
PLC
PLC
Other
equipment
Shared grounding
Good condition
Common grounding
Not allowed
Independent grounding
Best condition
Other
equipment
Other
equipment
BX
*1
S/S
4EX-BD
BX
*1
S/S
4EX-BD
3.4.2
In the case of input device with built-in parallel resistance
Use a device having a parallel resistance, Rp, of 15 k
Ω
or more.
If the resistance is less than 15 k
Ω
, connect a bleeder resistance, Rb (k
Ω
), obtained by
the following formula as shown in the following figure.
Sink input wiring
Source input wiring
*1 BX
:
represents the input number of 4EX-BD.
3.4.3
In the case of 2-wire proximity switch
Use a two-wire proximity switch whose leakage current,
, is 1.5 mA or less when the
switch is off. When the current is larger than 1.5 mA, connect a bleeder resistance, Rb
(k
Ω
), determined by the following formula.
Sink input wiring
Source input wiring
*1 BX
:
represents the input number of 4EX-BD.
4. Device allocation and program example
4.1 Device allocation
Each input of 4EX-BD is allocated a special auxiliary relay.
The ON/OFF state of each input is reflected in its corresponding special auxiliary relay.
4.2 Program example
Use a contact instruction for each special auxiliary relay.
4.3 Caution on Creation of Programs
•
When the END instruction of the program is executed, the input process is
completed.
REF instruction cannot be used.
•
When input information on 4EX-BD is used for the operand of each applied
instruction as data, only four bit data (K1M8112) can be used.
Input terminal
Special auxiliary relays
BX0
M8112
BX1
M8113
BX2
M8114
BX3
M8115
Rb(k
Ω
)
4Rp
15-Rp
BX
*1
S/S
4EX-BD
Rb
Rp
BX
*1
S/S
4EX-BD
Rb
Rp
I
Rb(k
Ω
)
6
I
-1.5
BX
*1
S/S
4EX-BD
Rb
BX
*1
S/S
4EX-BD
Rb
I
I
K100
When BX0 (M8112) is ON, drive M0.
M1
Y000
T0
M8112
M8113
M8114
M8115
When BX2 (M8114) is ON, drive Y000.
When BX1 (M8113) is ON, drive M1.
When BX3 (M8115) is ON, drive T0.
M0
5. Specification
5.1 Applicable PLC
The version number can be checked by monitoring D8001/D8101, as well the last three
digits indicate the version number.
•
Only one 4EX-BD can be used per main unit.
Never stack up two or more expansion boards.
For details on the system configuration, refer to the following manual.
→
FX
3S
Series User's Manual - Hardware Edition
→
FX
3G
Series User's Manual - Hardware Edition
5.2 General Specifications
The general specifications are equivalent to the PLC main unit.
For general specifications, refer to the following manuals.
→
FX
3S
Series User's Manual - Hardware Edition
→
FX
3G
Series User's Manual - Hardware Edition
5.3 Power Supply Specifications
5.4 Performance Specification
STARTUP AND
MAINTENANCE
PRECAUTIONS
•
Do not touch any terminal while the PLC's power is on.
Doing so may cause electric shock or malfunctions.
•
Before cleaning or retightening terminals, cut off all phases of the power supply
externally. Failure to do so may cause electric shock.
•
Before modifying or disrupting the program in operation or running the PLC,
carefully read through this manual and the associated manuals and ensure the
safety of the operation.
An operation error may damage the machinery or cause accidents.
STARTUP AND
MAINTENANCE
PRECAUTIONS
•
Do not disassemble or modify the PLC.
Doing so may cause fire, equipment failures, or malfunctions.
For repair, contact your local Mitsubishi Electric representative.
•
Do not drop the product or exert strong impact to it.
Doing so may cause damage.
DISPOSAL
PRECAUTIONS
•
Please contact a certified electronic waste disposal company for the
environmentally safe recycling and disposal of your device.
TRANSPORTATION AND
STORAGE PRECAUTIONS
•
The product is a precision instrument. During transportation, avoid impacts larger
than those specified in the general specifications by using dedicated packaging
boxes and shock-absorbing palettes. Failure to do so may cause failures in the
product. After transportation, verify operation of the product and check for damage
of the mounting part, etc.
Model name
Applicability
FX
3S
Series PLC
Ver. 1.10 or later
FX
3G
Series PLC
Ver. 2.20 or later
Item
Specification
Consumption
current
5 V DC
Supply by PLC.
24 V DC
25 mA max. Supply from external power supply.
Item
Specification
Number of input points
4 points
Input connecting type
Terminal block (European type)
Input form
Sink/Source
Input signal voltage
24 V DC +20 % -15 %
Input impedance
4.3 k
Ω
Input signal current
5 mA/24 V DC
ON input sensitivity current
3.5 mA or more
OFF input sensitivity current
1.5 mA or less
Input response time
Approx. 10 ms
Input signal form
Sink
No-voltage contact input
NPN open collector transistor
Source
No-voltage contact input
PNP open collector transistor
Input circuit insulation
Photocoupler insulation
Input operation display
LED lighting when photocoupler is driven
Number of occupied
I/O points
0 point (This number is not related to the maximum
number of input/output points of the PLC.)
「电器电子产品有害物质限制使用标识要求」的表示方式
Note: This symbol mark is for China only.
含有有害6物质的名称,含有量,含有部品
本产品中所含有的有害6 物质的名称,含有量,含有部品如下表所
示。
产品中有害物质的名称及含量
本表格依据SJ/T 11364的规定编制。
○:表示该有害物质在该部件所有均质材料中的含量均在GB/T
26572
规定的限量要求以下。
×:表示该有害物质至少在该部件的某一均质材料中的含量超出GB/T
26572规定的限量要求。
部件名称
有害物质
铅
(Pb)
汞
(Hg)
镉
(Cd)
六价铬
(Cr(VI))
多溴联苯
(PBB)
多溴
二苯醚
(PBDE)
可编程
控制器
外壳
○
○
○
○
○
○
印刷基板
×
○
○
○
○
○
Side
A
Side
B
JAPANESE
ENGLISH
JY997D51301C
Side
B
FX
3G
-4EX-BD
USER'S MANUAL
This manual describes the part names, dimensions, mounting, and specifications
of the product. Before use, read this manual and manuals of relevant products
fully to acquire proficiency in handling and operating the product. Make sure to
learn all the product information, safety information, and precautions.
Store this manual in a safe place so that it can be taken out and read whenever
necessary. Always forward it to the end user.
Registration:
The company name and the product name to be described in this manual are the
registered trademarks or trademarks of each company.
Effective December 2017
Specifications are subject to change without notice.
©
2013 Mitsubishi Electric Corporation
Manual Number
JY997D51301
Revision
C
Date
December 2017