HEAD OFFICE
: MITSUBISHI DENKI BLDG MARUNOUTI TOKYO 100-8310
TELEX : J24532 CABLE MELCO TOKYO
HIMEJI WORKS : 840, CHIYODA CHO, HIMEJI, JAPAN
FX
2NC
-485ADP
Installation Manual
JY997D01201B
This manual contains text, diagrams and explanations which will guide the reader in the correct
installation, safe use and operation of the FX
2NC
-485ADP (hereafter abbreviated to "485ADP") and should
be read and understood before attempting to install or use the unit. Further information can be found in
the associated manuals mentioned below.
Specifications are subject to change without notice
Safety guidelines for the user and protection of the FX
2NC
-485ADP.
This manual has been written to be used by trained and competent personnel. The definition of such a
person or persons is as follows:
a) Any engineer using the product associated with this manual, should be of a competent nature,
trained and qualified to the local and national standards. These engineers should be fully aware of
all aspects of safety with regards to automated equipment.
b) Any commissioning or service engineer must be of a competent nature, trained and qualified to
the local and national standards.
c)
All operators of the completed equipment should be trained to use that product in a safe and
coordinated manner in compliance to established safety practices.
Note:
The term ‘completed equipment’ refers to a third party constructed device which contains or uses
the product associated with this manual.
Notes on the Symbols Used in this Manual
At various times through out this manual certain symbols will be used to highlight points of information
which are intended to ensure the users personal safety and protect the integrity of equipment.
1) Indicates that the identified danger
WILL
cause physical and property damage.
2) Indicates that the identified danger could
POSSIBLY
cause physical and property
damage.
•
Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential damage
that may arise as a result of the installation or use of this equipment.
•
All examples and diagrams shown in this manual are intended only as an aid to understanding the
text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for the actual use of
the product based on these illustrative examples.
•
Please contact a Mitsubishi distributor for more information concerning applications in life critical
situations or high reliability.
Associated Manuals
PROGRAMMING MANUAL, PROGRAMMING MANUAL
ΙΙ
, or FX COMMUNICATION USER'S MANUAL
mentioned below are not provided in sets with a product.
Contact our agent where the product was purchased to request the manuals accordingly.
★
Indispensable manual
✩
Either manual is necessary.
Manual Name
Manual
Number
Description
This
manual
FX
2NC
-485ADP INSTALLATION
MANUAL
JY997D01201
Describes contents related to installation of the
FX
2NC
-485ADP Module.
★
FX COMMUNICATION USER'S
MANUAL
JY992D69901
Describes contents related to communication
available in FX Series PLC such as wiring,
communication setting, and program examples.
✩
FX
1S
HARDWARE MANUAL
JY992D83901
Describes contents related to hardware of FX
Series PLC such as specifications, wiring, and
installation.
✩
FX
0
/FX
0N
HARDWARE MANUAL
JY992D47501
✩
FX
1N
HARDWARE MANUAL
JY992D89301
✩
FX
2N
HARDWARE MANUAL
JY992D66301
✩
FX
2NC
HARDWARE MANUAL(DSS/DS)
(D/UL)
JY992D76401
JY992D87201
✩
PROGRAMMING MANUAL
JY992D76401
Describes contents related to instruction in FX
0
/
FX
0S
/FX
0N
/FX/FX
2
/FX
2C
Series PLC.
✩
PROGRAMMING MANUAL
ΙΙ
JY992D88101
Describes contents related to instruction in FX
1S
/
FX
1N
/FX
2N
/FX
2NC
Series PLC.
✩
FX
1N
-CNV-BD
Special Adapter Connection Board
JY992D84701
Describes contents related to installation of the
each board.
✩
FX
2N
-CNV-BD
Special Adapter Connection Board
JY992D63601
This manual describes the installation the and specifications of the 485ADP.
For details on wiring (including use of terminal resistor and preparation of cable) with communication equipment,
system configuration and communication setting, and program examples, refer to the "FX COMMUNICATION USER'S
MANUAL".
1. Outline of Product
The 485ADP is an insulated RS-485 communication adapter with an European type terminal block.
Connected to the main unit of the FX Series PLC, it enables signal exchange between the PLC and
equipment via an RS-485 port.
2. Communication Functions and Applicable PLC
(Available in indicated version or later)
3. Installation
Caution
• Use in the environments specified under the general specification in the manual.
Do not use the product in environments with excessive or conductive dust, corrosive or
flammable gas, oily smoke, moisture or rain, excessive heat, regular impact shocks or
excessive vibration, as it may result in electrical shock, fire, malfunction, damage or
deterioration on the product.
• Make sure to shut off the power outside the product before installing or wiring it.
Otherwise, electric shock or serious damage to the product may occur.
• Never drop wire chips or shavings into the vent slits when drilling screw holes or performing
wiring, as they may cause fire, breakdown, or malfunction.
• Securely install the 485ADP to the designated port.
Poor connection may cause malfunction.
3.1 How to Install to FX Series PLC
Installation to FX
1S
/FX
1N
/FX
2N
Turn OFF the PLC before beginning any work.
1) Remove the panel cover from the top face of the main unit.
2) Take off the resin cover from the left side of the main unit.
3) Install the following board to the port on the main unit.
4) Fix the above board using the M3 screws supplied.
Tightening torque: 0.3 to 0.6 N·m
5) Connect the in-built cable of the 485ADP to the port on the
board from the left side.
Installation to FX
0N
/FX
2NC
Turn OFF the PLC before beginning any work.
1) Remove the cover of the port for a special adapter provided on the left side of the main unit.
2) Connect the in-built cable of the 485ADP to the port for a special adapter.
3.2 How to Install to Panel Face
Direct installation to the panel face
Directly fix to the panel face using 2 sets of a screw (M4), a spring
washer, and a flat washer in the mounting holes.
Tightening torque: 0.7 to 1.0 N·m
For the pitch and positions of mounting screw holes, refer to the
external dimensions.
Mounting on DIN rail
Fix the 485ADP to the DIN rail, DIN46277 (35 mm (1.38 inches) wide).
Dismounting from DIN rail
Slightly pull down the DIN rail mounting clip using a tool such as a
slotted screwdriver. Pull down the clip further, and the rail will be locked
with the clip left open.
Communication
type
FX
0N
FX
1N
FX
1S
FX
2N
FX
2NC
Function
N:N network
V2.00
First
product
V2.00
First
product
Data transfer connecting up to eight FX Series PLCs.
Parallel link
V1.20
First
product
V1.04
First
product
Data transfer between two PLCs relationship specifying
master/slave station.
Computer link
V1.20
First
product
V1.06
First
product
Data transfer via link protocol between PLC and
computer (specified as the master station).
No protocol
communication
V1.20
First
product
V1.06
First
product
Serial communication without protocol between PLC
and equipment via RS-485 interface.
Inverter
communication
—
—
V3.00
V3.00
Controlling Mitsubishi's FREQROL inverter using
EXTR instruction in function expansion memory.
Board name
Corresponding model
FX
1N
-CNV-BD
FX
1N
, FX
1S
FX
2N
-CNV-BD
FX
2N
X
1
X3
Y
1
Y0
Y
2
1)
4)
5)
3)
2)
Installation to
FX
1S
/FX
1N
/FX
2N
(FX
2N
in the
diagram)
1)
2)
Installation to
FX
0N
/FX
2NC
(FX
2NC
in the
diagram)
FX
2NC
-
485ADP
Screws
FX Series PLC
RDA
RDB
SDA
SDB
SG
FX
2NC
-
485ADP
FX Series
PLC
DIN rail
Detach
To lock the tab
RDA
RDB
SDA
SDB
SG
RDA
RDB
SDA
SDB
SG
4. Product Specification
4.1 Specification
All other specifications than the followings are equivalent to those of the FX Series PLC main unit.
4.2 Outside Dimensions and Part Names
1) Mounting hole 2-
φ
4.2 (0.17)
Used when mounting the 485ADP directly.
Not used when mounting the DIN rail.
2) POWER LED
Lit while 5V DC power is supplied from main
unit.
3) RD LED
Lit while receiving data from connected
equipment via RS-485 port.
4) SD LED
L i t w h i l e s e n d i n g d a t a t o c o n n e c t e d
equipment via RS-485 port.
5) Cable
Used to connect to the main unit.
6) Terminal block for connecting RS-485
equipment (European type)
Used to connect RS-485 equipment to
485ADP.
7) DIN rail mounting clip
8) DIN rail mounting slot
4.3 Terminal configuration and recommended screwdriver
The terminal configuration of the RS-485 port on the 485ADP is as shown below.
Item
Specification
General
specification
Withstand voltage
500 V AC, 1 min (between terminal block and FX Series PLC main unit)
Insulation
resistance
5 M
Ω
or more, 500 V DC by Megger (between terminal block and FX Series
PLC main unit)
Power supply
specification
Power supply
voltage, current
5 V DC (supplied from PLC main unit), max. 150 mA
Performance
specification
Transmission
standard
Conforming to RS-485/RS-422
Type of isolation
Photo-coupler isolation
Transmission
distance
Total extension distance: 500 m or less
(50 m or less if FX
2N
-485-BD or FX
1N
-485-BD is installed in connected
equipment)
Connection method
European type terminal block, AWG 26-16 (when inserting one twisted pair
cable), AWG 26-20 (when inserting two twisted pair cables)
Tightening torque: 0.4 to 0.5 N·m
Number of
occupied I/O points
0 point (unrelated to maximum number of controlled points of the PLC)
Communication
method
Half-duplex
Baud rate
N:N network: 384000 bps, Parallel link: 19200bps
Computer link, No protocol: 300/600/1200/2400/4800/9600/19200 bps
Communication
format
N:N network, Parallel link
Computer (dedicated protocol: format 1/format 4), No protocol
LED display
(LED color)
Power: green, RD: red, SD: red
Signal
name
Function
Signal direction
485ADP
RS-485
equipment
RDA (RXD+)
Receive data
←
RDB (RXD-)
SDA (TXD+)
Send data
→
SDB (TXD-)
•
Not used
Do not wire.
SG (GND)
Signal ground
—
RDA
RDB
SDA
SDB
SG
74(2.91)
4
(0.16)
7(0.28)
(Height of screw hole)
16.1(0.63)
(to screw holes)
1)
2)
Unit: mm (inches)
19.1
(0.75)
7)
65.5(2.58)
(between screw holes)
10
(0.39)
90(3.54)
1)
Weight:
Approx. 0.1 kg (0.22 lbs)
Color:
Munsell 0.08GY 7.64/0.81
DIN rail width: 35 mm (1.38 inches)
Accessories: Terminal resistors (330
Ω
x 2 and 110
Ω
x 1),
Station number label for linking
3)
4)
5)
6)
8)
RDA
RDB
SDA
SDB
SG
Terminal
screws
0.6mm
(0.02")
3.5mm
(0.14")
The end
should be
straight.
Recommended screwdriver to
tighten terminal screws
Manual number : JY997D01201
Manual revision : B
Date