FX2N-64CL-M CC-Link/LT Master Block
Assignment of I/O numbers 8
8-2
8.2
Example of I/O number assignment
This paragraph describes I/O number assignment in the configuration example shown below.
The CC-Link/LT master function for the FX Series checks connected remote stations in the
CONFIG mode. At the next power ON, this master function assigns the I/O numbers to each
connected remote station. RD stations do not give any effect on assignment of the I/O
numbers because buffer memories (BFM) are assigned to RD stations in accordance with the
station number.
Assignment result
*1 With regard to X and Y, 8 points are occupied as 1 block. As a result, if the number of I/O
points occupied by a station is a number which cannot be divided by "8", unused numbers
are generated.
In the configuration example above, the I/O numbers are assigned as shown below.
Station type
Number of points I/O assignment (X) I/O assignment (Y) BFM #
Station No.1
Remote I/O station (input)
4 points
X040 to X043
--
--
Station No.2 Remote I/O station (output)
2 points
--
Y020, Y021
--
Station No.3
Remote I/O station (input)
16 points
X044 to X063
--
--
Station No.4
Remote I/O station
(input/output)
4 points
X064, X065
Y022, Y023
--
Station No.5
Remote I/O station (input)
4 points
X066 to X071
--
--
Station No.49
RD station (output)
16 points
--
--
208
Station No.50
RD station (output)
16 points
--
--
209
Unused I/O
*1
X072 to X077
Y024 to Y027
--
PLC
FX
2N
-32MT
I/O extension
block
FX
2N
-16EX
Master block
FX
2N
-64CL-M
The 16-point mode is selected because an RD station
is connected.
4 input
points
2 output
points
16 input
points
4 I/O
points
4 input
points
Terminal resistor
RD station
Output points
16 bits
×
2 ch
Terminal
resistor
Station
No.1
4 input
points
Station
No. 2
2 output
points
Station
No.3
16 input
points
Station
No. 4
4 I/O
points
Station
No.5
4 input
points
The 16-point mode is selected because an RD station
is connected.
Y000 to Y017 (octal)
X040 to X043
−
−
Y020 to Y021
X044 to X063
−
X064 to X065
Y022 to Y023
X066 to X071
−
X000 to X037 (octal)
PLC
FX
2N
-32MT
I/O extension
block
FX
2N
-16EX
Master block
FX
2N
-64CL-M
Terminal
resistor
RD stations
Nos. 49 and 50
Output points
16 bits
×
2 ch
Terminal
resistor
−
−
Summary of Contents for FX2N-64CL-M
Page 1: ...USER S MANUAL Detailed Volume FX2N 64CL M CC Link LT Master Block ...
Page 4: ...FX2N 64CL M CC Link LT Master Block ii ...
Page 6: ...FX2N 64CL M CC Link LT Master Block iv ...
Page 12: ...FX2N 64CL M CC Link LT Master Block x ...
Page 26: ...FX2N 64CL M CC Link LT Master Block System Startup Procedure 3 3 2 ...
Page 50: ...FX2N 64CL M CC Link LT Master Block Various Modes 7 7 2 ...
Page 74: ...FX2N 64CL M CC Link LT Master Block Model Assignment of Buffer Memory 10 10 14 ...
Page 93: ......