4 Specifications, External Dimensions and Terminal Layout (Main Units)
4.4 Output Specifications
FX
3U
Series Programmable Controllers
User’s Manual - Hardware Edition
4.4
Output Specifications
The main unit output specifications are explained below.
4.4.1
Relay output type
The output numbers in the table indicate the main unit terminal numbers. "Y010 or more" means the numbers
from Y010 to the largest number that the main unit has.
(The output numbers of FX
3U
-16MR/ES are Y000 to Y007.)
Item
Relay output specifications
FX
3U
-16MR/ S FX
3U
-32MR/ S
FX
3U
-48MR/
S
FX
3U
-64MR/
S
FX
3U
-80MR/
S
FX
3U
-128MR/ES
Number of output
points
8 points
16 points
24 points
32 points
40 points
64 points
Connecting type
Fixed terminal
block
(M3 screw)
Removable terminal block (M3 screw)
Output type
Relay
External power
supply
30V DC or less or 240V AC or less
(250V AC or less when the unit does not comply with CE, UL or cUL standards)
Max.
load
Resistance
load
2 A / point
The total load current of resistance loads per common terminal should be the following value.
→
For details on the common terminal for each model,
refer to the terminal block layout.
• 1 output point/common terminal: 2 A or less
• 4 output points/common terminal: 8 A or less
• 8 output points/common terminal: 8 A or less
Inductive
load
80 VA
→
For the product life, refer to Subsection 4.4.2.
→
For cautions on external wiring, refer to Subsection 12.2.4.
Min. load
5V DC, 2 mA (reference value)
Open circuit leakage
current
−
Response
time
OFF
ON
Approx. 10 ms
ON
OFF
Approx. 10 ms
Circuit insulation
Mechanical insulation
Display of output
operation
LED on panel lights when power is applied to relay coil.
Output circuit
configuration
External
power supply
Load
Fuse
Y
COM
DC power
supply
Fuse
Y
COM
A number (1 or more) is entered in of [COM ].
Load