FX
3U
Series Programmable Controllers
User’s Manual - Hardware Edition
176
9 Preparation for Wiring and Power Supply Wiring Procedures
9.3 Power Supply Specifications
9.3.2
DC Power Supply Type
*1.
This power consumption is the value maximized by input/output extension blocks and special function
units/blocks connected to the main unit.
→
For input/output powered extension units/blocks power consumption information,
refer to Section 15.2.
*2.
The power supply is not for external use.
The current capacity specified above is for the input/output extension blocks, special function blocks,
special adapters and expansion boards.
*3.
When supply voltage is 16.8 to 19.2V DC, the connectable extension equipment decreases.
For details, refer to Subsection 6.5.3 or 6.5.4.
Item
Specifications
FX
3U
-16M /D
FX
3U
-32M /D
FX
3U
-48M /D
FX
3U
-64M /D
FX
3U
-80M /D
Supply voltage
24V DC
Allowable supply voltage
range
16.8 to 28.8V DC
*3
Allowable instantaneous
power failure time
Operation can be continued upon occurrence of instantaneous power failure for 5 ms or less.
Power fuse
250V, 3.15A
250V, 5A
Power consumption
*1
25W
30W
35W
40W
45W
Rush current
35 A max. 0.5 ms or less/24V DC
24V DC service power
supply
−
5V DC built-in power
supply
*2
500 mA or less