FX0N-32NT-DP Profibus-DP Interface Unit
Setting Operation 5
5-3
5.2
Setting Slave Address in the 32NT-DP
When setting the DP-slave address from the PLC follow the example program.
Example program
The following is an example of how to set the slave address to “10” of a 32NT-DP connected
as block No.0.
Figure 5.1: Example Program
M8002
M1
FNC 78
FROM
K0
K30
D0
K1
FNC 10
CMP
D0
K7020
M0
FNC 79
TO
K0
K27
K10
K1
Initial pulse
The ID code for the 32NT-DP at
position “0” is read from BFM
#30 of that block and stored at D0 in
the main unit. This is compared
to check the block is a 32NT-DP, if
OK M1 is turned ON. These two
program steps are not strictly needed
to use the 32NT-DP. They are
however a useful check and are
recommended as good practice.
This command sets the slave
address to “10”.