![Mitsubishi FR-HEL Series Instruction Manual Download Page 21](http://html1.mh-extra.com/html/mitsubishi/fr-hel-series/fr-hel-series_instruction-manual_1809265021.webp)
4
Cable Size and Crimping Terminal
4
Cable Size and Crimping Terminal
Refer to
page 3
for the wiring of terminals P and P1 and the earthing cable.
(1) 200V class
* Torque value (reference value) for the iron screws with the 4.6 strength rating. Use the
tightening torque recommended for the applied screw (bolt).
Model
P, P1
Earth (Ground)
cable
Terminal
Screw
Size
Tightening
Torque
N
m
Crimp-
ing Ter-
minal
HIV
Cable
Size
(mm
2
)
Crimp-
ing Ter-
minal
Cable
Size
(mm
2
)
FR-HEL-0.4K to 2.2K
M4
1.5
2-4
2
2-4
2
FR-HEL-3.7K
M4
1.5
5.5-4
3.5
5.5-4
3.5
FR-HEL-5.5K
M4
1.5
5.5-4
5.5
5.5-4
5.5
FR-HEL-7.5K
M5
2.5
14-5
14
5.5-4
5.5
FR-HEL-11K
M6
3.8
14-6
14
8-6
8
FR-HEL-15K
M6
3.8
22-6
22
14-6
14
FR-HEL-18.5K
M8
13.2 *
38-8
38
14-6
14
FR-HEL-22K
M10
26.5 *
38-10
38
22-6
22
FR-HEL-30K
M10
26.5 *
60-10
60
22-6
22
FR-HEL-37K
M10
26.5 *
80-10
80
22-6
22
FR-HEL-45K, 55K
M12
46.1 *
100-12
100
38-6
38
FR-HEL-75K
M12
46.1 *
150-12
125
38-6
38
FR-HEL-90K
M12
46.1 *
150-12
150
38-6
38
FR-HEL-110K
M12
46.1 *
100-12
100
2
60-6
60